Warnings
In order to avoid the danger of electrical shock, it is important
that proper safety measures are taken when working with
voltages exceeding the extra low voltage (ELV) limit of 50V AC
RMS or 120V DC.
Where applicable other safety measures such as use of protective
gloves, goggles etc. should be employed.
This socket tester must only be used by a skilled and competent
person who is familiar with the relevant regulations, the safety
risks involved and the consequent normal safe working practices,
and under the conditions and for the purposes for which it has
been constructed and specified.
Before each use the socket tester should be examined for
damage, cracks, cuts or scratches. Do not use if damaged in
any way.
Make sure the socket tester is dry, clean and free from dust,
grease and moisture while in use to avoid the danger from electric
shock due to surface leakage.
The EZ165 & EZ365 must only be used on CAT II installations up
to 300V to earth.
Always verify the unit is functioning correctly on a known correctly-
wired live socket before and after use.
If none of the indicators illuminate, this does not necessarily
mean the circuit under test is dead. For example the earth and
neutral lines could both be open circuit, or the supply voltage
may be <135V.