Earth loop threshold accuracy: ± (10% + 0.3Ω)
Voltage low indication: <195V ± 5%
Voltage high indication: >270V ± 5%
Earth neutral voltage high indication: >30V ± 5%
Open earth indication: >500Ω ± 10%
Note 1: Measurement accuracy can be affected by highly inductive or
capacitive loads distributed on the supply (see section 3.3.4).
General
Dimensions: 65 x 80 x 59mm
Weight: approx. 93g
Environmental
Temperature (Operating & Storage): -10°C to 40°C, at max. 60% RH
Altitude: up to 2000m
Pollution degree: 2
Safety
Conforms to BS EN 61010-1, CAT II 300V
Class II, double insulation
EMC
Conforms to BS EN 61326-1
Specification
EZ165
E-ZE Check Xtra
Electrical
Nominal operating voltage: 230V AC rms
Operating frequency: 50Hz
Power consumption: <2.5W
Power: from mains socket under test
Non-trip earth loop impedance ranges:
0 - 1.7 - 5 - 10 - 100 - 200 - 500Ω