Specifications - Martindale Electric EZ365 Instruction Manual

Socket tester
Hide thumbs Also See for EZ365:
Table of Contents

Advertisement

Earth loop threshold accuracy: ± (10% + 0.3Ω)
Voltage low indication: <195V ± 5%
Voltage high indication: >270V ± 5%
Earth neutral voltage high indication: > 30V ± 5%
Open earth indication: >500Ω ± 10%
RCD test current at 195V: 30mA
Duration of RCD test current: 300ms
Polarity reversal test
Note 1: Measurement accuracy can be affected by highly inductive or
capacitive loads distributed on the supply (see section 3.3.6).
General
Dimensions: 65 x 80 x 59mm
Weight: approx. 93g
Environmental
Temperature (Operating & Storage): -10°C to 40°C, at max. 60% RH
Altitude: up to 2000m
Pollution degree: 2
Safety
Conforms to BS EN 61010-1, CAT II 300V
Class II, double insulation
EMC: Conforms to BS EN 61326-1
Specification
EZ365
E-ZE Check Xtra
Electrical
Nominal operating voltage: 230V AC rms
Operating frequency: 50Hz
Power consumption: <2.5W
Power: from mains socket under test
Standby: after approx. 10 minutes
Non-trip earth loop impedance ranges:
0 - 1.7 - 5 - 10 - 100 - 200 - 500Ω
Note 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents