USER MANUAL Edition: 1 from 19.02.2022 Supersedes edition: Power supplies PSDCG2 series Buffer power supply units, multi-output enclosed Grade 2...
Features: compliance with norm EN50131-6:2017 function START allows running PSU from battery power in grade 1, 2 and II environmental class dynamic battery test compliance with norm EN60839-11:2013 battery circuit continuity control in grade 1, 2 and II environmental class battery voltage control ...
To be able to install PSU module in the Intrusion Detection Systems or Access Control systems, it must be placed in enclosure with an appropriate design and, in order to obtain certificate, supplementary tests must be commissioned for compliance with EN50131-6: 2017 or EN60839-11: 2013 standards in notified laboratory.
Fig. 2a. View of power supply module PSDCG2-12V4x1A Fig. 2b. View of power supply module PSDCG2-12V8x1A Fig. 3a. View of power supply module outputs PSDCG2-12V4x1A Fig. 3b. View of power supply module outputs PSDCG2-12V8x1A 1.4. Specifications: - electrical parameters (tab. 3 ) - operation safety (tab.
Page 5
Table 3. Electrical parameters. Model PSDCG2-12V4x1A PSDCG2-12V8x1A PSU type A (EPS - External Power Source), II environmental class Power supply ~ 200 - 240 V Current consumption 0,7A 1,3A Power frequency 50/60 Hz Inrush current 40 A Output power PSU 138W Output current 4x1 A...
2. Installation. 2.1 Requirements. Buffer power supply is designed to be installed only by qualified installer with necessary permits and authorisations (required in installation country) to connect (interfere) with the 230 V mains supply. The unit should be mounted in confined spaces, in accordance with the II environmental class, with normal relative humidity (RH=90% maximum, without condensing) and temperature from -10°C to +40°C.
3.1 Optical indication. The power supply unit features LED status indication. Presence of voltage at output of the PSU is indicated by the green LED L1 ÷ Ln. Failure (fuse damage) is indicated by shutting illuminating the red LED FPS. Status of the PSU (fuse damage AUX1 ÷...
CAUTION! The power supply module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law. Pulsar sp. j. Siedlec 150, 32-744 Łapczyca, Poland Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 e-mail: biuro@pulsar.pl,...