NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Figure 4-3 Space requirements
(1) NetCol5000-A
4.1.4 Outdoor Unit Installation Position
Precautions
●
●
●
●
Special Environment Requirements
●
Issue 04 (2022-12-15)
Ensure that air smoothly flows into and out of the condenser. Install an
outdoor unit in clean areas that are away from residential areas.
When the outdoor unit is installed horizontally or vertically, the horizontal or
vertical error should be no more than ±5°.
When routing pipes for the condenser, ensure that the pipes are routed in
from the top and out from the bottom.
When the device is installed vertically, ensure that the electric control box and
its waterproof connector do not face upwards.
Figure 4-4 Installation mode (using the NetCol500-A060 as an example)
Monsoon: If you install the outdoor unit vertically, ensure that the air
produced by fans flows in and out in the same direction as the monsoon.