NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Tab
Issue 04 (2022-12-15)
Parameter
DO_2
DO_1 action
DO_2 action
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_2 acts according to
DO_2 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_2 acts according to
DO_2 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_2 acts according to
DO_2 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_2 acts according to DO_2
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_2 acts according to
DO_2 action when the unit is
started.
● If this parameter is set to Power
abnormal, DO_2 acts according to
DO_2 action when a power
exception alarm is generated.
● If this parameter is set to No, no
alarm is generated when DO_2 is
disconnected.
This parameter can be set to On or
Off, and is used together with DO_1.
For details, see DO_1 description.
This parameter can be set to On or
Off, and is used together with DO_2.
For details, see DO_2 description.
115