Low Temperature Component - Huawei NetCol5000-A050 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual (1350 mm Depth)
Type
Class C (harsh environment)
Class D (marine environment)

3.3 Low Temperature Component

Figure 3-6 Dimensions
BOM number
Issue 04 (2022-12-15)
NO TE
● If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being
corroded by sea wind (the functionality and reliability of the system must not be
affected). Alternatively, use an outdoor unit that supports class C environments to avoid
corrosion. If the site is more than 10 km away from the coast, the unit can be properly
installed.
● The NetCol500-A060MS1E0 outdoor unit must not be installed in class D environments,
and other outdoor units must not be installed in class C or class D environments.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Sea environments or outdoor land
environments (with simple shielding measures)
near pollution sources. Pollution sources refer
to the following areas:
● Areas within 3.7 km away from saline water
areas such as the ocean and saline lakes
● Areas within 3 km of serious pollution
sources, such as metallurgic plants, coal
mines, and heat and power plants
● Areas within 2 km away from medium
pollution sources, such as chemical
factories, rubber plants, and electroplating
factories
● Areas within 1 km away from light pollution
sources, such as food factories, tanneries,
and heating boilers
Areas within 500 m away from the seashore.
52271197
3 Technical Specifications
41