NI SC Express Considerations
PXI clock and trigger signals are only available on PXI Express devices.
PXI and NI SC Express Clock and Trigger Signals
PXIe_CLK100
PXIe_CLK100 is a common low-skew 100 MHz reference clock for synchronization of
multiple modules in a PXI Express measurement or control system. The PXIe backplane is
responsible for generating PXIe_CLK100 independently to each peripheral slot in a
PXI Express chassis. For more information, refer to the PXI Express Specification at
www.pxisa.org
PXIe_SYNC100
PXIe_SYNC100 is a common, low-skew 10 MHz reference clock with a 10% duty cycle for
synchronization of multiple modules in a PXI Express measurement or control system. The
PXI Express backplane is responsible for generating PXIe_SYNC100 independently to each
peripheral slot in a PXI Express chassis. For more information, refer to the PXI Express
Specification at
PXI_CLK10
PXI_CLK10 is a common low-skew 10 MHz reference clock for synchronization of multiple
modules in a PXI measurement or control system. The PXI backplane is responsible for
generating PXI_CLK10 independently to each peripheral slot in a PXI chassis.
PXI_CLK10 cannot be used as a reference clock for SC Express modules.
Note
© National Instruments Corporation
.
.
www.pxisa.org
3-1
3
NI PXIe-4300 User Manual