12.4. Fan Operation

• Fan operation can be set using remote control.
• The indoor fan is operated at High, Medium or Low speed according to remote control setting.

12.5. Thermostat Control

• Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
• If temperature difference matches values shown below, thermostat switches off.

12.6. Indoor Fan Control

• Manual Fan Speed
Operation starts at High, Medium or Low speed set by remote control.
• Auto Fan Speed
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, indoor fan operates as below.
Thermostat &
Compressor ON/OFF
Time
Cooling
Auto
Soft Dry
Auto

12.7. Odour Cut Control

• Odour cut operation removes the odour generated at indoor heat exchanger by using drain water come out from indoor heat
exchanger.
• Press "Odour" button at remote control to enable odour cut operation.
• Odour cut operation starts when compressor or thermostat is on.
Thermostat &
Compressor ON/OFF
Time
Cooling
Soft Dry
Cooling
Soft Dry
Thermostat & Compressor ON
40 sec.
50sec.
Off
SSLo
Hi
Off
SSLo
SLo
Thermostat & Compressor ON
40 sec.
50sec.
Off
SSLo
Normal
Operation
Off
SSLo
SLo
Thermostat & Compressor OFF
-
20 sec.
160 sec.
SSLo
Off
SSLo
Off
Thermostat & Compressor OFF
-
20 sec.
160 sec.
SSLo
Off
SSLo
Off
29
0°C
-1.0°C
Thermostat & Compressor ON
20 sec.
40 sec.
SSLo
Off
SSLo
Off
Thermostat & Compressor ON
20 sec.
40 sec.
SSLo
Off
SSLo
Off
50 sec.
-
SSLo
Me
SSLo
SLo
50 sec.
-
SSLo
Normal
Operation
SSLo
SLo