36 Electrical planning guidelines

Separate control cable ducts

Put 24 V DC and 230 V AC (120 V AC) control cables in separate ducts, unless the 24 V DC
cable is insulated for 230 V AC (120 V AC) or insulated with an insulation sleeving for
230 V AC (120 V AC).

Roxtec cable entry option +H394

The cabinet can be equipped with a multi-cable transit frame for Roxtec cable entry
(option +H394). ABB provides only the frames, not the seals nor the installation tools.
For sealing components and installation instructions, refer to www.roxtec.com.
The figure below shows a bottom cable entry frame and and an example of a sealing
module for a W600 cabinet.
The table below lists the Roxtec cable entry frames for different cabinet sizes.
Designed for
Cabinets with bottom cable entry
ACS880LC W300
TBA
3AUA5000221237
ACS880LC W400
(kit)
ACS880LC W500
3AUA5000118748
3AUA5000320033
ACS880LC W600
(kit)
24 V DC
Cable frame
Roxtec frame
S 8X1 AISI316
S 6X2 AISI316
S 8X1 AISI316
S 8X3 AISI316
GH8X2 AISI316
5GH0000008124
230 V AC
24 V DC
(120 V AC)
230 V AC
(120 V AC)
ABB designed flange and Roxtec frame
welded together.
ABB designed flange and Roxtec frame
welded together.
Roxtec frame with integrated flange.
ABB designed flange and Roxtec frame
welded together.
Description

Advertisement