Cable type
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and symmetrically
constructed PE conductor and a
shield (or armor)
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and a shield (or ar-
mor), and separate PE conduct-
1)
or/cable
1) A separate PE conductor is required if the conductivity of the shield (or armor) is not sufficient for the PE use.

Alternate power cable types

Exception for ACS880-304LC...+A019 diode supply modules: These power cable types
are not allowed.
Cable type
EMT
Four-conductor cabling in metal
conduit (three phase conductors
and PE). For example, EMT, or
four-conductor armored cable
Shielded (Al/Cu shield or armor)
four-conductor cable (three phase
conductors and a PE)
Use as input power cabling
Yes
PE
Yes
PE
Use as input power cabling
Yes
Yes
1)
Electrical planning guidelines 29
Use as motor cabling and as
brake resistor cabling
Yes
Yes
Use as motor cabling and as
brake resistor cabling
Yes with phase conductor smaller
2
than 10 mm
(8 AWG) Cu, or mo-
tors up to 30 kW (40 hp)
Yes with motors up to 100 kW
(135 hp). A potential equalization
between the frames of motor and
driven equipment is required.