8.6 LCD settings configuration
There are 10 UPS settings that can be configured by the user.
1.
Press the "ENTER" button simultaneously for 5 seconds to activate
the setting mode. The first configuration parameter will be displayed
on the LCD screen.
NOTE!
The manual settings programming mode can ONLY be invoked while UPS is
in Bypass mode or Standby mode. To make UPS on Standby mode or Bypass
mode, connect utility power to UPS and do not turn on UPS.
2.
Press the "ENTER" button to select the setting you want to
configure.
3.
Press the "ENTER" buttons to scroll through the different
parameters and select the parameter you want.
4.
Press the "ESC" button for 5 seconds to cancel and exit setting
mode. Press the "ENTER" button for 5 seconds to save all the
settings you just do and exit setting mode.
5.
In any mode(Except setting mode), Press the "ESC" button
simultaneously for 5 seconds to disable and enable buzzer alarm
Setting
Configure
item
Submenu
Output
001
Voltage
Output
002
Frequency
ECO
003
Mode *
Bypass
004
Mode **
Available Settings
=[208V] [220V] [230V]
[240V]
= [50Hz][60Hz]
[0%] (Disable) [10%][15%]
(Enable)
[DIS] (Disable) [ENA]
(Enable)
Default
LCD Display
Setting
0 0 1
230V
230
00 2
50Hz
00 3
0%
00 4
Enable
EnA
23
50
0