Njoy Aster Series User Manual page 21

Hide thumbs Also See for Aster Series:
Table of Contents

Advertisement

Available languages

Available languages

8.4 Event ID descriptions
Event ID
Description of Cause
Bus Start Fail: DC-DC converter or bus sensing circuit
E01
failed.
E02
Bus Volt High: DC-DC converter failed.
E03
Bus Volt Low: DC-DC converter failed.
E04
Bus Unbalanced: DC-DC converter failed.
E06
INV Start Fail: Inverter circuit failed.
INV Volt High: Inverter circuit or output voltage sensing
E07
circuit failed.
INV Volt Low: The load may be too heavy or inverter
E08
circuit failed.
E09
INV Short: The inverter circuit failed.
Bat Volt High: The external battery module connection is
E11
wrong, or the charger failed.
E12
Bat Volt Low: Batteries failed.
E14
Over Load: UPS is overloaded.
Fan Fail: The ventilation hole has been covered, or the
E18
fans can't work.
Over Temperature: High ambient temperature, or the
E19
ventilation hole has been covered.
A56
Bat Volt Low: Battery voltage is low.
A57
Bat Cap Low: Battery capacity is low.
A59
Bat Disconnect: Battery is disconnected.
A60
Overcharge: Charger voltage is high.
A61
Charger Fail: Charger is failed.
A62
Bat Bad: Battery failed.
21