5.8.1 Removal

FIRST REMOVE
1. Remove motor (subassembly #4). (See Section 4.1.1)
2. Remove Accutronix control panel (subassembly #7). (See Section 5.1.1)
3. Remove control module (subassembly #15). (See Section 5.4.1)
4. Remove contractor assembly (subassembly #8). (See Section 5.5.1)
STEP 1
If worm shaft assembly (subassembly #3) is still mounted in unit,
remove the four screws (#3-9) and rotate cap (CCW) to rotate
cap tab away from motor lead seal.
STEP 2
Remove motor lead harness by threading the harness back through
housing and out motor end. Work the three connectors out through
the hole/slot in the housing one at a time.
Accutronix MX Maintenance & Spare Parts Manual
130-12000 Revision B • November 2002
Flow Control Division
Limitorque Actuation Systems
Electronic Assemblies
1
2
cap tab
motor
lead
seal
5-33