Electronic Assemblies
STEP 10
Insert retaining ring (#1-21) into retaining ring groove –
snap retaining ring into groove by working a flat blade
screwdriver around the edge of the retaining ring until it
seats into groove.
STEP 11
If contactor assembly was loosened in Step 7, then remount
contactor on screws (#8-28). Retighten with M3 hex key.
STEP 12 & 13
Connect incoming power leads and control wiring according
to application wiring diagram if terminal block has been
replaced.
Install the terminal compartment cover and secure with
four M8 screws using a 6 mm hex key.
5-22
Accutronix MX Maintenance & Spare Parts Manual
Flow Control Division
Limitorque Actuation Systems
10
11
12, 13
130-12000 Revision B • November 2002
1-21