5.2.5.4 Adding Electronic Option to Your Accutronix MX Actuator
Listed below are the options available for the Accutronix MX.
1. Modutronic option; does not require any hardware, however, a "keycode" from the
factory is required.
2. 2-speed timer; does not require any hardware, however a "keycode" from the factory is
required.
3. APT option; Analog Position Transmitter, non-contracting 4-20 mA position transmitter
requiring the addition of the I/O (input/output) option board.
4. ATT option; Analog Torque Transmitter, non-contacting 4-20 mA torque transmitter
requiring the addition of the I/O (input/output) option board.
5. AR option; Alarm Relays, (3) non-latching relays requiring the addition of the I/O
(input/output) board. Non-latching relays change state when power is removed from the
actuator, e.g. if the relay is CLOSED & power is removed, the relay will OPEN.
6. DDC option; network communication field board that is required for 2-wire twisted pair,
MODBUS communication.
7. FF option; network communications board required for Foundation Fieldbus
communication.
The procedure for adding electronic options to your MX actuator is as follows:
• For adding the Modutronic and 2-speed timer options, the actuator QA Stamp ID must be supplied
in order to acquire the necessary keycode.
• Each MX actuator is supplied a unique "QA Stamp ID". This number is assigned
during the END-OF-LINE test sequence for each unit.
• This serial number is located on the second screen after the "RESTRICTED SETTINGS"
screen. It is an eight (8) digit number after the letters "S/N". Please refer to the I&O
manual, 130-11000, supplied with your actuator for the Menu sequence.
• User must supply this number. Example: 12345678
• Also record the Order Number & Serial Number of the actuator.
These numbers can be found on the unit nameplate.
• Once you have acquired the QA Stamp, O/N & S/N, please contact your assigned Service
Coordinators for the keycodes required to turn-on the desired options @ (434) 528-4400.
• The "keycode" is then entered into the desired option menu found in "RESTRICTED
SETTINGS" using the black knob on the ACP. A "NO" answer will change the value form 0-9 and A-E. A
"YES" answer will truncate to the next space.
• After enabling the Modutronic option, please change the remote control wiring scheme to "3-wire
maintained."
• For adding the APT, ATT, and AR options, the I/) option board is required. When the I/O
board is received and installed into the actuator, it will already have the option(s) enabled.
The unit will recognize the board and turn on the required software menu feature. Please
refer to the I&) manual, 130-11000, supplied with your actuator for the Menu sequence.
The user will need to enable the menu options. Please contact your assigned Service
Coordinators for purchase of these desired options @ (434) 528-4400.
• For adding the DDC or FF option, the DDC or FF option board is required. When the DDC
option board is received and installed into the actuator, it will recognize the board and
turn on the required software menu feature. Please refer to the I&O manual, 130-11000,
supplied with your actuator for the Menu sequence. The user will need to enable the menu options.
Please contact your assigned Service Coordinators for purchase of the DDC option @ (434) 528-4400.