Snap-in I/O Modules
Increasing Contact Life Span
To increase the life span of the relay output
contacts and protect the device from potential
damage by reverse EMF, connect:
a clamping diode in parallel with each
inductive DC load,
an RC snubber circuit in parallel with each
AC
inductive
load.
Transistor Outputs
Each output can be wired separately as either npn or pnp.
The 0V signal of the transistor outputs is isolated from the controller's 0V signal.

Analog Inputs

Shields should be connected at the signal source.
Inputs may be wired to work with either current or voltage.
Note that the analog input's 0V signal must be the same 0V used by the controller's power supply.
Unitronics
npn (sink)
current
pnp (source)
current/voltage