Pt100/1000 Inputs - Grundfos CRE Installation And Operating Instructions Manual

E-pumps with mle frequency-controlled permanentmagnet motors
Table of Contents

Advertisement

Sensor function/measured parameter
"Inlet pressure"
"Diff. press., inlet"
"Discharge press."
"Diff. press., outlet"
"Diff. press, pump"
"Press. 1, external"
"Press. 2, external"
"Diff. press., ext."
"Storage tank level"
"Feed tank level"
"Pump flow"
"Flow, external"
"Liquid temp."
"Temperature 1"
"Temperature 2"
"Diff. temp., ext."
"Ambient temp."
"Other parameter"
"Unit"
Parameter
Possible units
Pressure
"bar", "m", "kPa", "psi", "ft"
Level
"m", "ft", "in"
Pump flow
"m³/h", "l/s", "yd³/h", "gpm"
Liquid temperature
"°C", "°F"
Other parameter
"%"
"Electrical signal"
Select signal type:
"0.5-3.5 V"
"0-5 V"
"0-10 V"
"0-20 mA"
"4-20 mA".
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See "Limit 2 exceeded" in the section on factory settings.
Related information
3.2.2 Identification of functional module
8.13 "External setpoint function"
8.41 "Assisted pump setup"
8.42 "Setup, analog input"
9.2 Factory settings

8.6 "Pt100/1000 inputs"

Pos.
Available inputs depend on the functional module fitted in the pump:
1
2
Function (terminal)
3
4
"Pt100/1000 input 1, setup" (17
5
and 18)
6
"Pt100/1000 input 2, setup" (18
and 19)
7
8
1)
See the section on the identification of functional module.
9
If you want to set the Pt100/1000 input for a feedback sensor, we
10
recommend that you do this via the "Assisted pump setup" menu.
See the section on assisted pump setup.
11
If you want to set a Pt100/1000 input for other purposes, you can do
12
this manually.
13
You can set the analog inputs via the "Setup, analog input" menu.
See the section on setting up the analog input.
14
If you make the manual setting via Grundfos GO Remote, you need
15
to enter the menu for the Pt100/1000 input under the "Settings"
16
menu.
Not shown
Function
Not shown
The Pt100/1000 inputs can be set to these functions:
"Not active"
"Feedback sensor" The sensor is used for the selected control
mode.
"Ext. setpoint infl." See the section on the external setpoint
function.
"Other function".
Measured parameter
Select one of the parameters listed below, i.e. the parameter to be
measured in the system by the PT100/1000 sensor connected to
the actual PT100/1000 input. See the figure below.
Overview of PT100/1000 sensor locations
Parameter
"Liquid temp."
"Temperature 1"
"Temperature 2"
"Ambient temp."
Measuring range
-50 to 204 °C.
Factory setting
See the section on factory settings.
Related information
3.2.2 Identification of functional module
8.13 "External setpoint function"
8.41 "Assisted pump setup"
8.42 "Setup, analog input"
9.2 Factory settings