GRUNDFOS INSTRUCTIONS CRE, CRIE, CRNE, CRKE, SPKE, MTRE E-pumps with MLE Model K frequency-controlled permanent- magnet motor North America Installation and operating instructions CRE, CRIE, CRNE, CRKE, SPKE, MTRE Installation and operating instructions Other languages http://net.grundfos.com/qr/i/92898117...
Page 3
CRE, CRIE, CRNE, CRKE, SPKE, MTRE English (US) Installation and operating instructions ............4 Appendix A .
Grundfos' The symbols and hazard statements below may appear in Grundfos warranty. Grundfos will not be liable for damage or wear to products installation and operating instructions, safety instructions and caused by abnormal operating conditions, accident, abuse, misuse, service instructions.
The pumps have been factory-set to constant-curve control mode. SELV single-fault conditions, including earth faults in You can change the control mode with Grundfos GO, HMI 300, HMI other circuits. 301 or Grundfos GO Link. Safe Torque Off. A sub safety function, where a 3.1.2 Pumps with a factory-fitted pressure sensor...
Status. other MLE motors. Motor nameplate The product contains a class 1 radio. Grundfos will You can identify the fitted module by means of the data on the support the product with security updates for at least 2 motor nameplate.
Safe Torque Off ‐ Keep a safe distance to the product during lifting Installation and operating instructions operations. http://net.grundfos.com/qr/i/92916582 ‐ Follow the lifting instructions for the product. 3.8.1 Identification of the Safe Torque Off (STO) function WARNING The version of the Safe Torque Off (STO) function is marked on the Back injury nameplate, after the product version number.
5. Installation requirements • Keep cooling fins and fan blades clean. 5.1 Installing the product in areas with high humidity WARNING Fire hazard Death or serious personal injury ‐ In high humidity environments where condensation can occur, connect the product permanently to the power supply and activate the standstill heating function.
6. Mechanical installation 6.1.1.2 Drain holes The motor has a plugged drain hole on the drive side. The drain 6.1 Mounting the product hole is placed in the flange on the drive side. You can turn the flange 90° to both sides or 180°. WARNING With the drain hole open, the motor becomes self-venting, allowing Crushing of feet...
Page 11
2. Remove the terminal box cover. Model K 6. Fit the terminal box cover and make sure that it is turned 180° so that the buttons on the operating panel are aligned with the buttons on the plastic cover. 7. Tighten the four screws (TX25) with 3.7 ft⋅lb (5 Nm). Model K 3.
If you the power supply for the signal relays. Wait at least 5 are in doubt, contact Grundfos. minutes before you make any connections in the terminal box. Make sure that the power supply cannot Only the following motors can be supplied through an IT network: be switched on accidentally.
Protective-earth conductors must have a yellow and green (PE) or 7.8.3 Cable cross-section yellow, green and blue (PEN) colour marking. WARNING 7.5 Cover for the power cables Electric shock Model K is equipped with a cover for the power cables. Death or serious personal injury The cover is attached to the insulation cover with 2 screws (2) and ‐...
Page 14
7.8.3.1 Cable cross-section data for MLE motors 3 × 440-480 V, 60 Hz, Model K Service factor Speed Power P2 Supply voltage Nominal current Cable cross-section current [rpm] [HP] [AWG] 3 × 440-480 23.1 - 21.8 27.3 - 24.8 3500-4000 3 ×...
7.8.4 Conductors The product is protected against transients from the power supply according to EN 61800-3. In areas with high Conductor types lightning intensity, we recommend external lightning Model K: Use stranded copper conductors only. protection. Overvoltage category: Conductor temperature ratings The product is approved for Overvoltage category III rating.
Page 16
LIVE: You can connect supply voltages up to 250 VAC to the output. • Grundfos Digital Sensor input and output SELV: The output is galvanically separated from other circuits. • two Pt100/1000 inputs Therefore, you can connect the supply voltage or safety extra-low •...
Page 17
• 0.5 - 3.5 V, 0-5 V or 0-10 V. +5 V Power supply to a potentiometer or sensor Signal ground GDS TX Grundfos Digital Sensor output GDS RX Grundfos Digital Sensor input Signal ground Digital input/output, configurable DI4/OC2 Open collector: Maximum 24 V resistive or inductive...
Grundfos Eye is off The power is off. Operation Pump running Ready Alarm Warning Operating mode Grundfos Eye is rotating green The pump runs in Normal mode in open or closed loop. Operation Pump running Ready Alarm Warning Operating mode Normal Min.
Page 19
Grundfos Eye is rotating yellow Warning, but the pump is running. Operation Pump running Ready Alarm Warning Operating mode Manual Grundfos Eye is permanently yellow Warning, but the pump was stopped via a Stop command. Operation Pump running Ready Alarm...
E-pump. The brown wire of the pressure sensor is connected to terminal 24 V of the E-pump. 7.13.3 Connecting a 2-core bus cable 7.12.3 Connection of Grundfos pressure sensor ISP44 to an E- • Connect a screened 2-core bus cable as follows: pump 7.13.4 Bus signal...
Contact Grundfos for further information. If you use a bus signal, the local settings made via Grundfos GO or the HMI 300 or 301 operating panel will be overruled. In case the bus signal fails, the product will run with the local settings made via Grundfos GO or the HMI 300 or 301 operating panel.
7. Connect the cable screens of the bus cables to protective earth 8. Starting up the product via one of the earth clamps (H). WARNING Rotating parts Death or serious personal injury ‐ Make sure to install the coupling guards before powering on the product.
Up/Down: The buttons change the setpoint. Communication: The button enables communication with Grundfos GO and other products of the same type. Start/Stop: Press the button to make the product ready for operation or to start and stop the product. Start: If you press the button when the product is stopped, the product starts if no other functions with higher priority have been enabled.
Page 24
- Press the Start/Stop button. Max. - Press and hold the Down button until all light fields are off. - Use Grundfos GO. - Use a digital input set to External stop. 9.2.7 Resetting alarms and warnings in products with the HMI 200 or 201 operating panel •...
When you try to establish radio communication between the product and Grundfos GO or another product, the green indicator light in Grundfos Eye flashes. In the controller display, a note states that a device wants to connect to the product. Press OK on the product operating panel to allow communication with Grundfos GO or Grundfos GO Link and other products of the same type.
Page 26
9.3.1 Home display Status Settings Assist Setpoint Control mode 5.00 bar Const. pressure Pos. Symbol Description Home: This menu shows up to four user-defined parameters. You can access each parameter directly from this menu. Operaring mode Actual controlled value Status Settings Assist Status: This menu shows the status of the product and system, warnings and alarms.
Page 28
Settings Single pump Multipump system Relay output 1 • • Relay output 2 • • • • Analog output • • Output signal Function of analog output • • Controller settings • • Operating range • • Setpoint influence • •...
Page 29
Assist Single pump Multipump system Assisted pump setup • • Setup, analog input • • Setting of date and time • • Setup of multi-pump system • • Description of control mode • • Assisted fault advice • •...
Const. pressure the product with Grundfos GO. GO using Bluetooth (BLE). Press the Home button to reject Grundfos GO enables you to set functions and gives you access to connection. status overviews, technical product information and current Operaring mode Actual controlled value operating parameters.
Page 31
9.4.2 Menu overview for Grundfos GO Dashboard Single pump Multipump system • • View all metrics Single pump Multipump system Pump and application Actual controlled value • • Acc. flow, specific energy • • Energy consumption • Energy consumption, system •...
Page 32
• Time for pump changeover • Inputs/outputs Analog input 1 • Analog input 2 • • Analog input 3 Built-in Grundfos sensor • Analog output • • Pt100/1000 input 1 • Pt100/1000 input 2 Digital input 1 • Digital input 2 •...
• 9.5 Grundfos GO Link The product is designed for wired or wireless communication with Grundfos GO Link. Grundfos GO Link enables you to set functions and gives you access to status overviews, configuration and current operating parameters. Ethernet Use Grundfos GO Link together with these interfaces: •...
Link is wired to the pump within a short distance, no verification is needed. A direct connection will be established. 9.6 Grundfos Eye The operating condition of the motor is indicated by Grundfos Eye on the motor operating panel. Grundfos Eye indicator light (A)
Page 35
Grundfos GO. The green indicator light in the You have selected the motor in Grundfos GO, and the motor is ready middle is flashing continuously. to be connected.
When you have set the operating mode to Manual, the product starts running at the set speed. With Grundfos GO, you can set the speed via the Setpoint menu.
Page 37
Constant pressure This control mode requires an external pressure sensor as shown in the examples below. You can set the pressure sensor in the Assist Controller settings menu. See the section on assisted pump setup. The setting range For the recommended controller settings, see the section on the is between 12.5 % and 100 % of maximum head.
Page 38
Constant differential-pressure control is achievable with two You can set the sensor manually or by using the Assist menu. individual pressure sensors. The pump uses the inputs from the See the section on assisted pump setup. two sensors and calculates the differential pressure. The sensors must have the same unit and must be set as feedback sensors.
Factory setting See the section on factory settings. Related information 10.57 Factory settings for Grundfos GO 10.8 Automatic Night Setback Once you have enabled automatic night setback, the pump automatically changes between normal duty and night setback, duty 10.6 Setting the proportional pressure at low performance.
Feedback sensor The sensor is used for the selected control mode. Related information • Setpoint influence 10.57 Factory settings for Grundfos GO The input signal is used for influencing the setpoint. 10.9 Analog inputs • Other function The inputs and outputs available depend on the functional module The sensor input is used for measurement or monitoring.
Electrical signal The sensor input is used for measurement or monitoring. Available signal types: Measured parameter • 0.5 - 3.5 V Select one of the below parameters to be measured in the system • 0-5 V by the sensor connected to the input. •...
FM311 • • Open contact. Selecting the trigger function can only be set via Grundfos GO Link. Wiring example: The digital inputs can be activated either as active low or active high. The digital inputs will react as described in the table below:...
10.11.1 Timer function for a digital input 10.12 Digital inputs/outputs The inputs and outputs available depend on the functional module Activation delay fitted in the motor. The activation delay (T1) is the time between the digital signal and the activation of the selected function. Digital input/output 3 Digital input/output 4 Functional...
• Limit 1 exceeded • Digital input 3, state Follow digital input 3. If digital input 3 is triggered, the digital • Limit 2 exceeded output is also triggered. • Digital input 1, state • Digital input 4, state • Digital input 2, state Follow digital input 4.
If the controller is hunting or unstable, dampen the system by L1: Distance in feet between the pump and the sensor. reducing the gain or increasing the integral time. Factory setting See the section on factory settings. Related information 10.57 Factory settings for Grundfos GO...
Pt100/1000 inputs. To enable the function, set one of the analog inputs or Pt100/1000 inputs to Setpoint influence with Grundfos GO or to Ext. setpoint infl. with the HMI 300 or 301 100 % operating panel.
10.17.1.3 Influence table Pos. Description The setpoint is influenced by a curve made of two to eight points. External input signal from 0 to 100 % There is a straight line between the points and a horizontal line Setpoint influence from 0 to 100 % before the first point and after the last point.
The function requires setting of the following parameters: If all digital inputs are open, the motor stops or runs at the normal setpoint. Set the desired action with Grundfos GO or with the HMI Measured 300 or 301 operating panel.
Related information The function is to monitor the outlet pressure from the pump. If the 10.57 Factory settings for Grundfos GO pressure is below 72 psi (5 bar) for more than 5 seconds, a warning is indicated. If the pressure is above 101 psi (7 bar) for more than 8 10.22 Stop function (Low-flow stop function)
81 (307) Factory setting See the section on factory settings. Related information 10.57 Factory settings for Grundfos GO Position of the non-return valve and pressure sensor in system 10.23 Stop at min. speed with suction lift operation This stop function can be utilised in for example constant level applications where a boost of pressure is not needed.
Related information pressure sensor of the system detects that the pipes have been filled, phase two begins. 10.57 Factory settings for Grundfos GO 2. Pressure build-up phase. The system pressure is increased until 10.25 Pulse flowmeter (Pulse flowmeter setup) the setpoint is reached. The pressure build-up takes place over a pressure build-up time.
Analog input 2 relubricated. • Analog input 3 10.33 Communication • Built-in Grundfos sensor Use this function to set the communication of the product, both • Pt100/1000 input 1 wired and wireless communication. The product contains built-in • Pt100/1000 input 2 fieldbus protocols on the AYB terminals (RS-485).
Page 53
Radio communication remains active. 10.33.4 Initiate Bluetooth connection Use this function if Grundfos GO is installed on Huawei smartphones with BLE version 5.0 or older. This function is used to establish a Bluetooth connection to Grundfos GO. Open the...
DNS must be configured manually. • If you use Grundfos GO and set the buttons to Not active, the buttons on the HMI 200 or 201 operating panel are disabled, 10.33.6.3 IP address except the Radio communication button.
• Controller settings • Summary of settings. With Grundfos GO, access the Assisted pump setup menu. With the HMI 300 or 301 operating panel, access the Assisted pump setup menu. 10.51 Setup, analog inputs This function is only available in the HMI 300 and 301 operating panels.
1. Power on both motors. • Alternating operation, time 2. Establish contact to one of the motors with Grundfos GO. The change from one pump or motor to the other is based on time. 3. Set the needed analog and digital inputs via Grundfos GO according to the connected equipment and the required •...
Page 57
10. Press OK or the Radio communication button on the motor which is to be added to the multimotor system. 3. Establish contact to one of the motors with Grundfos GO. 11. Press the Right button to continue. 4. Set the required analog and digital inputs via Grundfos GO according to the connected equipment and the required 12.
4. Press OK to confirm No multi-pump function. 5. Press the Right button to continue. 6. Press OK to confirm. 10.54 Description of control mode The function is only available in the HMI 300 and 301 operating panels. The function describes each of the control modes available for the product.
Start Stop and Maximum speed settings made with Grundfos GO or on the motor operating panel can be overruled by another operating-mode command sent from a bus, for example Start. If the bus communication is interrupted, the motor resumes its previous operating mode, for example Stop, that was selected...
10.57 Factory settings for Grundfos GO Settings With factory-fitted sensor Without factory-fitted sensor Setpoint 75 % of sensor range 75 % speed Operating mode Normal Normal Set user-defined speed 67 % 67 % Control mode Constant pressure Constant curve Pipe-filling function...
11. Servicing the product WARNING Crushing of feet WARNING Death or serious personal injury Electric shock ‐ Wear safety shoes. Death or serious personal injury ‐ When lifting the motor, attach lifting equipment to the ‐ Switch off the power supply to the product including eye bolts fitted to the motor.
11.1 Maintenance 11.1.1 Cleaning the product WARNING Electric shock Death or serious personal injury ‐ Switch off the power supply to the product including the power supply for the signal relays. Make sure that the power supply cannot be switched on accidentally. ‐...
-4 °F (-20 °C) Related information 122 °F (50 °C) 2.1 Related instructions Maximum 7.11 Signal relays 9.6 Grundfos Eye 35 HP MLE motors are rated for a maximum value of 104 °F (40 °C). 14. Technical data 14.1.4 Humidity 14.1 Operating conditions Description Percentage 14.1.1 Installation altitude...
14.2.1 Leakage current (AC) For recommended size of fuses see the appendix The leakage currents are measured without any load on the shaft concerning installation in the USA and Canada. and in accordance with EN 61800-5-1:2007. WARNING Electric shock Death or serious personal injury ‐...
Use Pt1000 for long wires. LiqTec sensor inputs Use a Grundfos LiqTec sensor only. Screened cable: 0.5 - 1.5 mm / 28-16 AWG. Grundfos Digital Sensor input and output (GDS) Use Grundfos Digital Sensor only. Power supplies, +5 V, +24 V +5 V •...
Page 66
C2/C3 C2/C3 Depending on product hardware configuration. Immunity: The motor fulfils the requirements for industrial areas. 14.4.6 Cable entry sizes Contact Grundfos for further information. Number and size of cable entries 14.4.3 Enclosure class Motor Number and size of Supply voltage...
QR code app. 1. Use the public or private waste collection service. 2. If this is not possible, contact the nearest Grundfos company or service workshop. 3. Dispose of the waste battery through the national collective schemes.
Page 69
3 × 440-480 V 1750 2200 2200 3500 4000 4000 1750 2200 2200 3500 4000 4000 1750 2200 2200 3500 4000 4000 To be determined. Check the online version. CRE, CRIE, CRNE, CRKE, SPKE, MTRE installation and operating instructions http://net.grundfos.com/qr/i/92898117...
Page 70
8 inches (20 cm) between the radiator and your body. This device complies with Part 15 of the FCC rules and RSS210 of the IC rules. Changes or modifications made to this equipment not expressly approved by Grundfos may void the FCC authorization to operate this equipment.
Page 71
Cet appareil est conforme à la section 15 de la réglementation FCC et à RSS210 de la réglementation IC. Les changements ou modifications apportés à cet équipement qui ne sont pas expressément approuvés par Grundfos peuvent annuler l'autorisation de la FCC à utiliser cet équipement.
Page 72
Torques See the section on torques. Line reactors The maximum line reactor size in front of the drive must not exceed the following values: Model K Maximum line reactor size [mH] [kW] [HP] 3500-4000 rpm 18.5 Line reactors are often required for six-pulse variable speed drives. Please observe that the MGE, MLE utilize a small DC capacitor concept for lower harmonics and exceeding the maximum inductance may cause resonance between reactor and the MGE, MLE that will reduce the lifetime of the product.