Connecting The External Fast Stop Cabling - SMA SUNNY CENTRAL 500CP XT Installation Manual

Hide thumbs Also See for SUNNY CENTRAL 500CP XT:
Table of Contents

Advertisement

SMA Solar Technology AG
Procedure:
1. Lead the external voltage supply cable into the interface cabinet (see Section 12.2, page 55).
2. Connect the cable in accordance with the circuit diagram (see Section 12.3.1, page 55).
3. Attach the cable to the cable support rail using a cable tie. This will ensure that the cable cannot be pulled out
inadvertently.

12.3.9 Connecting the External Fast Stop Cabling

If required, you can connect an external fast stop in accordance with the circuit diagram. The fast stop can be operated
by means of an internal or external voltage supply.
Shortfall of external supply voltage
If an external supply voltage of between 18.5 V and 24.0 V is supplied to the external fast stop, the Sunny Central
will continue to operate in its current operating state. If the external supply voltage to the external fast stop falls
below 18.5 V, the Sunny Central switches from the current operating state to the operating state "Stop".
If the temperature in the interior of the Sunny Central exceeds +60°C, the external fast stop must be supplied with
a supply voltage between 20.0 V and 24.0 V to continue operating the Sunny Central in its current operating state.
• Ensure that the external fast stop is supplied with a constant external voltage between 20.0 V and 24.0 V.
Cable requirements:
☐ The cable must be shielded.
Cable requirements for internal voltage supply:
☐ Maximum cable length with cable cross-section of 2.5 mm
☐ Maximum cable length with cable cross-section of 1.5 mm
Requirements:
☐ The Sunny Central must be disconnected (see Section 14, page 65).
☐ Use latching switches only.
Procedure:
1. Insert the cable of the external fast stop into the interface cabinet (see Section 12.2, page 55).
2. Connect the cable in accordance with the circuit diagram (see Section 12.3.1, page 55).
3. Attach the cable to the cable support rail using a cable tie. This will ensure that the cable cannot be pulled out
inadvertently.
Installation Manual
12  Cable Connection of External Devices and Connections in the Interface Cabinet
2
: 130 m
2
: 80 m
SCCPXT-IA-D7-en-42
61