Accuracy
Status indication
Input cable length
RTD Inputs
Number of inputs
RTD Type
Input range
Galvanic isolation
Conversion method
Resolution
Conversion time
Input impedance
Auxillary current
Accuracy
Status indication
Notes:
6.
The device can also measure resistance within the range of 1-320Ω
at a resolution of 0.1Ω.
7.
The input analog value represents the temperature value as follows:
Analog Value: 260
8.
The analog value can indicate faults as shown below:
Thermocouple Inputs
Number of inputs
Input range
Isolation
Conversion method
Resolution
Conversion time
Input impedance
Cold junction compensation
Cold junction compensation error
Absolute maximum rating
Accuracy
Warm-up time
Status indication
Notes:
9.
The device can also measure voltage within the range of -5 to 56mV, at a resolution of
0.01mV. The device can also measure raw value frequency at a resolution of 14-bits
(16384). Input ranges are shown in the following table:
14
 3%
Yes – if an analog input deviates above the permissible range, its
value will be 1024/4096 (depends on the selected resolution).
Up to 30 meters, shielded twisted pair
JZ20-UA24 / JZ20-J- UA24
PT100
-200 to 600C/-328 to 1100F. 1 to 320Ω. See Note 6
None
Voltage to frequency
0.1C/0.1F - See Note 7
300mS minimum per channel, depending on software filter type
>10MΩ
150μA typical
±0.44%
Yes. See Note 8
Value
Possible Cause
32767
Sensor is not connected to input, or value exceeds permissible range
-32767
Sensor is short-circuited
JZ20- UA24/ JZ20-J-UA24
See Note 9
None
Voltage to frequency
0.1C/ 0.1F maximum. See Note 10
100mS minimum per channel, depending on software filter type
>10MΩ
Local, automatic
±1.8C / ±3.24F maximum
±0.6VDC
±0.44%
½ hour typically, ±1C/±1.8F repeatability
Yes. See Note 11
2
Actual measured temperature: 26.0C
2
Installation Guide
JZ20-UN20 / JZ20-J-UN20
1
JZ20-UN20 / JZ20-J-UN20
1
Unitronics