Initial Startup

5.2
1. Obtain the startup password through the app. After the application is approved, enter the
password on the service authorization screen of the device to complete device authorization.
Technical support engineers can obtain the service authorization code through the app. For
details, see the
Data Center Facility Deployment Guide
2. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
3. After you perform the settings, the Bypass mode
and No battery alarms are reported by the MDU
and do not need to be cleared. If there is any
other alarm, you need to rectify the fault.
4. If the system has connected to the remote EPO switch, you need to choose Monitoring > UPS
System > Running Parameter > System Settings on the WebUI and set EPO detection to
Enable.
5. View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
5.3
Starting inverter
1. On the main menu, choose Common Functions and
tap Inv. ON.
2. In the displayed login window, enter the user name and
password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
.
10
.
To ensure system security,
change the LCD and WebUI
passwords after the first login.