Single Line Diagram; Getting Started - Energizer HOMEPOWER HP-6S Installation Manual

Table of Contents

Advertisement

1
Rated Energy is determined as per battery standard IEC 62619:2017.
Usable Capacity is calculated as 95% of Rated Energy.
2
HP-6S unit is considered a sub-system of the Main Unit (HP-6M) and is never installed in a stand-alone manner.
3
4
Performance de-rating expected in extreme ambient temperature.
Nominal Output Voltage
Nominal AC Frequency
PF Range
Grid
(AC Input)
Rated Power
3600 W
Max. Active Power
6000 W
Max. Apparent Power
6000 VA
Rated Apparent Power
6000 VA
Rated AC Current
26 A a.c.
Over Current Protection
26 A
THD Index
Max Efficiency
Standby Self Consumption
Inrush Current
Topology
Fault Current
Grid Terminal: 48.08Apeak (25.42ms)
Backup Load Terminal: 76.39Apeak (10s)
Anti-islanding Method
Method (a) - frequency shift as per Clause 4.3 in AS/NZS 4777.2:2020 is in use
DRM Support Method
HP-6M
Battery Type
Battery Energy
Nominal Voltage
230 V d.c.
Rated Charge Current
Rated Discharge Current
Rated Current (AC Input)
Rated Apparent Power (AC Output)
Rated Current (AC Output)
Voltage Range
Number of Cells
Standby Self Consumption
Battery Short Circuit Current
Additional Features
Supported Communication
2.4G Wi-Fi, RS 485, Ethernet, CTs,
Interfaces
CAN (to battery), Cellular/4G (to Cloud)
Communication Module
Integrated Communications Module (supporting LTE-TDD/ FDD, UMTS/
HSPA+, GSM/GPRS/EDGE) with external Antenna
Monitoring
Energizer Homepower Monitoring (App & Web platform)
500A±50A: primary short-circuit protection performed by BMS (Electronic).
5
8500A: prospective short-circuit current with no protection.
6
Table 1. Electrical Specifications
V23-00220
6
Energizer Homepower HP-
Series - Installation Manual
Inverter
230 V a.c.
50 Hz (Self-Adapting)
1 (adj 0.8 leading – 0.8 lagging)
Grid
Backup/UPS
(AC Output)
(AC Output)
3600 W
3600 W
3600 W
3600 W
3600 VA
3600 VA
3600 VA
3600 VA
16 A a.c.
16 A a.c.
18 A
16.45 A
< 3%
94%
<10 W
<10 A
High Frequency Isolation
DRMs (0-8)
Battery
HP-6S
LFP (Lithium Iron Phosphate)
6.14kWh
51.2 V d.c.
71 A d.c.
71 A d.c.
16 A a.c.
3600 VA
16 A a.c.
41 V – 57.6 V d.c.
16
< 3W (Standby)
500±50A
/ 8500A
5
6
RS 485, CAN 2.0
(To Inverter)
12
© Energizer 2022
Energizer Homepower HP-

Single Line Diagram

The Energizer Homepower HP-6 Series is designed to operate as an AC coupled BESS in conjunction with an
existing solar PV inverter. It has a single phase 3.6 kW integrated inverter that charges and/or discharges the
battery using a proprietary algorithm. The Energizer Homepower HP-6 Series system can be installed on sites with
either single, dual or three phase service connections. For simplicity, the diagram below captures the electrical
N/A
connections required for an installation at a site with a single-phase service connection.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Within Australia & New Zealand, the neutral cables emerging from the Grid/Backup terminals on the
HP-6M must be connected externally on the neutral bar (MEN link) within the switchboard. Please
refer to your local and national codes for relevant regulations. Refer to Page 35 for more information
regarding RCD requirement.

3. Getting Started

The Energizer Homepower HP-6 Series system is designed for both indoor & outdoor installations and relies on
Current Transformers (CTs) to monitor solar production & utility grid-based consumption. The location of the
installation must be chosen as per the site conditions, but it is recommended to install the HP-6 system within the
vicinity of the Main Service Panel/Switchboard (MSB).
The Energizer Homepower HP-6M is equipped with an integrated communications module that supports WiFi,
4G/LTE or Ethernet to enable an internet connection. The communication module can support only one type of
connection at a time, and it is recommended to select the applicable wireless standard based on the site conditions
and available wireless connectivity. It is essential to connect the HP-6 system to the Energizer Homepower Cloud to
enable real-time monitoring and remote device troubleshooting. In areas or regions with weak 4G/LTE signal, CAT-
5E cables can be used to connect the HP-6 system to a Wi-Fi router at the property.
The AC isolation and interconnection requirements between the HP-6 system and the Main Switchboard are
N/A
subject to the local codes & standards. Ensure that the installation meets the local isolation and interconnection
requirements & also conform to the laws, regulations, codes & applicable standards.
N/A
WARNING! The Energizer Homepower HP-6 Series system is designed to operate mainly on
a single-phase service connection and does not support Multiple Inverter Combinations
as described in AS/NZS 4777.2:2020 (Section 5). When Installing on a multi-phase service
connection, ensure you do not install more than one Main Unit (HP-6M).
V23-00220
6
Series - Installation Manual
Fig. 4. Energizer Homepower HP-6 System Schematics
13
© Energizer 2022