Commissioning
5.3
Overview Basic Setup
D
LN
L
LB
24
flange:
reference point of
measurement
UB
SD
E = empty calibr. (= zero)
setting in 005
F = full calibr. (= span)
setting in 006
D = distance (distance flange / product)
display in 0A5
L
= level
display in 0A6
Levelflex M FMP41C 4...20 mA HART
E
F
LN = probe length
setting in 033
UB = upper blocking distance
setting in 059
SD = safety distance
setting in 015
LB = lower blocking
distance
L00-FMP4xxxx-19-00-00-en-039
Endress+Hauser
Need help?
Do you have a question about the HART Levelflex M FMP41C and is the answer not in the manual?