No. Installer Setting
33
Compressor
Balance Point
[Only available for 2 or 3 stage heat pump systems with a Braeburn
use of the heat pump compressor's heat stage(s) when the outside air temperature is less than the selected setting. During
this lockout period, only the auxiliary heat stage will operate.
34 Auxiliary Heat
Balance Point
'
[Only available for 2 or 3 stage heat pump systems with a Braeburn 5490 outdoor sensor connected] Locks out
the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting. This balance point
overrides the fossil fuel compressor lockout in setting 16. If setting 16 is set to gas and the outdoor temperature is over
the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
35
Heat Setpoint
Upper Limit
Selects the upper setpoint adjustment limit that cannot be exceeded in heat mode.
36
Heat Setpoint
Lower Limit
Selects the lower setpoint adjustment limit that cannot be exceeded in heat mode.
37
Cool Setpoint
Lower Limit
[Not available for heat-only hydronic systems] Selects the lower setpoint adjustment limit that cannot be
exceeded in cool mode.
38
Cool Setpoint
Upper Limit
[Not available for heat-only hydronic systems] Selects the upper setpoint adjustment limit that cannot be
exceeded in cool mode.
39
Installer Lock
When enabled, a 4-digit lock code can be entered in setting 40. This lock code will be required the next time the
Installer Settings menu is accessed. Select NO to skip the installer lock.
40
Installer Lock Code
[Only available if Installer Lock was enabled in setting 39] Select a 4-digit lock code (0-9 for each digit) to
lock the Installer Settings menu. The code 0000 is not a valid lock code and cannot be used.
41
Installer Clear
(factory reset)
Selecting ALL will return thermostat to all factory default settings. Factory reset will take affect upon exiting
Installer settings menu.
Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings – See User Manual.
Displayed
Default Available
Setting
BALPOINT
NO
COMP
BALPOINT
NO
AUX
HIGH LIM
90
HEAT
LOW LIM
45
HEAT
LOW LIM
45
COOL
HIGH LIM
90
COOL
INSTLOCK
NO
IL CODE
0000
CLEAR
NONE
Description of
Settings
Available Settings
NO
Compressor balance point is disabled
0 to 50
Select a Compressor Balance Point of 0˚ to
(-18˚ to 10˚C) 50˚ (-18˚ to 10˚C)
5490 outdoor sensor connected] Locks out the
®
NO
Auxiliary heat balance point is disabled
70 to 40
Select a Auxiliary Heat Balance Point of
(21 ˚ to 4˚C) 70° to 40°F (21° to 4°C)
90 - 45 Select a Heat Setpoint Upper Limit of 90° to
(32˚ to 7˚C) 45°F (32° to 7°C)
45 - 90 Select a Heat Setpoint Lower Limit of 45° to
(7˚ to 32˚C) 90°F (7° to 32°C)
45 - 90 Select a Cool Setpoint Lower Limit of 45° to
(7˚ to 32˚C) 90°F (7° to 32°C)
90 - 45 Select a Cool Setpoint Upper Limit of 90° to
(32˚ to 7˚C) 45°F (32° to 7°C)
NO
Installer Lock disabled
YES
Installer Lock enabled
0-9
Select 0-9 for each digit
NONE Clear disabled - No changes made
ALL
Clear enabled - Factory Reset
13
Installer Manual