Ceraphant T PTC31, PTP31, PTP35
W-Code
W107
W202
W209
W210
W212
W250
W270
W280
7.2
Repair
A repair is not planned.
7.3
Disposal
When disposing, ensure that the materials of the device components are separated and processed
accordingly.
7.4
Change status (release)
The release number on the nameplate and in the Operating Instructions indicates the change
status of the device: X.YY. (example 1.02. ).
X
Change in the main version.
Compatibility no longer provided. Device and Operating Instructions change.
YY
Compatibility provided. Operating Instructions change.
Endress+Hauser
Explanation
Simulation active
Pressure outside the sensor range
Device starts
Configuration modified (warning code will be
displayed for 15 s approx.)
Sensor signal outside the permitted range
Number of switch cycles exceeded
Short-circuit and overload at output 1
Short-circuit and overload at output 2
Remedy
Switch off the output simulation for output 1
and output 2
Operate the device in the specified pressure
range
Operate the device in the specified pressure
range
Replace the device
Check output wiring. Extend the load
resistance at output 1
Check output wiring. Extend the load
resistance at output 2
Trouble-shooting
27