Download Print this page
turck FMX-IM-2UPLI63FX Quick Start Manual

turck FMX-IM-2UPLI63FX Quick Start Manual

Flow monitoring - for the connection of intrinsically safe flow sensors hart device with current and transistor outputs

Advertisement

Quick Links

FMX-IM-2UPLI63FX
Flow Monitoring – For the Connection of Intrinsically Safe
Flow Sensors
HART Device with Current and Transistor Outputs
Technical data
Type
ID
Electrical data
Operating voltage
Power consumption
No-load current I
0
Teach modes
Flow speed
Medium temperature
Repeatability flow rate
Repeatability media temperature
Measuring accuracy media temperature
Switchpoint hysteresis media tempera-
ture
Input function
Sensor voltage
Sensor current
Sensor current limitation
Measuring frequency
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 1|4
FMX-IM-2UPLI63FX
100000823
 
20...30  VDC
< 10.5 W
≤ 63 mA
Min/max adjustment. Teach modes incl.
DeltaFlow monitoring (teach modes are
automatically released with the change of
flow speed).
[%] after min/max adjustment (perma-
nent)
[°C] with the SET button temporarily
pressed
typical ± 1 % (of full scale)
typical ± 1 K
typical ± 7 K
2 K
Connection of flow sensors (excluding
non-Ex sensors from the FP100 product
series)
≤ 7 VDC
≤ 70 mA
approx. 110 mA
5 Hz (every 200 ms with software filter)
Features
For Ex ia resp. Ex ib sensors
Analog output for flow
Transistor outputs for temperature and
faults
Teaching upper and lower flow limit
LED band for indication of flow speed and
media temperature
Monitoring of operating and display range
Detection of wire-break and short-circuit on
the sensor side
Parametrized via pushbutton and FDT/DTM
Associated equipment [Ex ia Ga / Da]
Connection of flow probes Zone 0 / 20
Functional principle
All Ex flow sensors from the FCS series
(immersion sensors) and FCI series (inline
sensors) can be operated with the FMX-IM
external processing unit.
 
The flow module features four status LEDs
as well as a 10-segment LED band for local
monitoring. Software-based diagnostic options
are also available to the user, such as wire-
break and short-circuit on the sensor side.
Furthermore, monitoring of flow rates and
media temperatures within a predefined
operating and display range.
 
The upper and lower limit are determined
in relation to the analog output signal and
taught in using the implemented teach mode.
Working on the calorimetric principle, the
connectible sensors not only detect the flow
rate but also the media temperature.
 
The parameterization can be carried out via
touch buttons or software-supported via the
communication interface HART, which is then
carried out via the device-specific DTM within
the FDT frame PACTware.

Advertisement

loading
Need help?

Need help?

Do you have a question about the FMX-IM-2UPLI63FX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for turck FMX-IM-2UPLI63FX

  • Page 1 Sensor current limitation approx. 110 mA Measuring frequency 5 Hz (every 200 ms with software filter) Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 1|4...
  • Page 2 Mounting type DIN rail mounting and mounting panel Protection class IP20 MTBF 108  Years Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 2|4...
  • Page 3 HART-capable Turck devices; galvanic separation between the device to be parametrized and the PC Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 3|4...
  • Page 4 Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed. Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com 4|4...