3.11.2 Repair procedures

To remove the reactor
To install the reactor
Service manual
112
Is the continuity measurement correct? Action
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see
2 Open the compressor insulation.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
3 Remove the cover of the compressor wire terminals.
a Compressor wire terminals cover
4 Disconnect the connector.
5 Remove the clip and remove the reactor from the compressor.
6 To install the reactor, see
1 Install the reactor in the correct location and install the clip.
2 Connect the reactor connector.
3 Install the cover of the compressor wire terminals.
Return to the troubleshooting of the
specific error and continue with the
next step.
Replace the reactor, see
procedures" [
"3.10 Plate
a
"3.11.2 Repair
procedures" [
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
"3.11.2 Repair
4
 112].
work" [
4
 100].
4
 112].