3.14 Thermistors

3.14.1 Refrigerant side thermistors

Checking procedures
To perform a mechanical check of the specific thermistor
Service manual
118
4 Connect the swing raster motor rod to the swing raster shaft using soft tools.
5 Install the swing raster motor assembly on the correct location in the indoor
unit using the 2 screws.
a Swing raster motor cover
b Swing raster motor assembly
c Screw
6 Tighten the 2 screws that fix the swing raster motor to the bracket.
7 Install the swing raster motor cover.
8 Install the switch box, see
Is the problem solved?
Yes
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Locate the thermistor and remove the insulation if needed. Check that the
thermistor is correctly installed and that there is thermal contact between the
thermistor and the piping or ambient (for air thermistor).
b
c
a
4
"3.10 Plate
work" [
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
 100].
4
"3.10 Plate
work" [
 100].
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01D – 2022.02