Two Rdu40 Connected To The Same Rex - Emerson ROSEMOUNT TankRadar REX RDU 40 User Manual

Table of Contents

Advertisement

Rosemount Tank Radar REX
Chapter 1 Installation
The RDU40 housing shall be grounded locally to the tank. Use minimum
4 mm
power distribution central or the REX junction box is not recommended
except where required according to national code of practice. A ground
loop with circulating current may occur.
If a cable with two shields is used, one shield shall be connected to
ground in the REX junction box and the other shall be circular connected
inside the cable gland of the RDU40.
Check the packing and put the locking device for the weather protection
hatch in position when remounting the RDU-cover. Tighten all six screws
firmly.
Mount the RDU40 with the four M4 screws. Distances between the
screws are 60 mm and 68 mm, see Figure 1-2.
Figure 1-2. Back of RDU40.
1.1

Two RDU40 connected to the same REX

If two RDU40 are to be installed to the same REX one of them has to be
"slave" while the other is "master". The slave cannot be configured or
controlled individually but follows the master. Only the LCD-contrast can
be individually controlled at the slave.
To make an RDU40 work as a slave it is necessary to move the jumper at
the RDU40 cover to position 2 according to Figure 1-1.
1-2
2
or AWG 11 wire. Additional protective ground connection to the
User's Guide
308010EN, Edition 2
July 2007