Technical White Paper
Item
Acoustic noise
Corrosive gaseous
contaminant
Particulate pollutant
Issue 02 (2019-03-13)
Specifications
The following data is the declared A-weighted sound power
levels (LWAd) and declared average bystander position A-
weighted sound pressure levels (LpAm) when the server is
operating at 23°C (73.4°F). Noise emissions are measured
in accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
Idle:
l LWAd: 7.1 Bels
l LpAm: 57.3 dBA
Operating:
l LWAd: 7.2 Bels
l LpAm: 58.4 dBA
NOTE
The actual sound levels generated when the server is operating vary
depending on the server configuration, workload, and ambient
temperature.
l Copper corrosion rate test requirements: The corrosion
product thickness growth rate is lower than 300 Å/
month (meeting level G1 requirements of the ANSI/
ISA-71.04-2013 standard on gaseous corrosion).
l Silver corrosion rate test requirements: The corrosion
product thickness growth rate is lower than 200 Å/
month.
l The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
You are advised to ask a professional organization to
monitor particulate pollutants in the equipment room.
l There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
Copyright © Huawei Technologies Co., Ltd.