Follow the installation procedure described below:
1.
assemble the SA0 steam distributor (see paragraph 1.4.2 Assembling
the frame, SA0 versions);
2.
apply the drilling template to the duct where the steam distributor will
be installed;
3.
drill the required holes;
4.
insert the gasket and rest it against the support flange;
5.
insert the fastening screws to secure the support flange;
6.
place the upright in the 100 mm opening made in the duct;
7.
fasten the support flange screws to 7-8Nm (5-6ft), using the fastening
elements supplied;
8.
If necessary, secure the end of the upright.
See "SA0 installation procedure - manifold outside of AHU - with AHU wall
cover kit" at the end of the manual for details.
Installation inside the air handling unit
Follow the installation procedure described below:
assemble the SA0 steam distributor (see paragraph 1.4 Assembling the
frame, SA0);
prepare the suitably sized and spaced supports so as to fasten the
support flange and the end of the upright (supports not supplied);
If necessary, secure the end of the upright.
1.7.2

SA0 (single-pipe) minimal clearances

Correct installation of the SA0 distributor means allowing for certain
minimum clearances.
H
H
Effective single upright flow-rate ≤ 50kg/h (110lb/h) -> H=150mm (5.9in)
Minimum AHU height: 300mm (11.8in)
Effective single upright flow-rate > 50kg/h (110lb/h) -> H=200mm (7.9in)
Minimum AHU height: 400mm (15.8in)
H
H
"ultimateSAM - user" +03U0070EF - rel. 2.0 - 20150301
Fig. 1.t
H
H
H
H
H
H
H
H
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=250mm (9.8in)
Minimum AHU height: 400mm (15.8in)
H
H
Effective single upright flow-rate > 50kg/h (110lb/h)
H
H=150mm (5.9in) L=250mm (9.8in)
Minimum AHU height: 450mm (17.7in)
L
H
H
H
L
H
H
H
L
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=160mm (6.3in)
Minimum AHU height: 460mm (18.1in)
L
L
Effective single upright flow-rate > 50kg/h (110lb/h)
H
H
H=200mm (7.9in) L=200mm (7.9in)
Minimum AHU height: 600mm (23.6in)
L
H
L
H
L
L
H
H
*Note: Not available in North American market; for illustration
purposes only.
H
SAKD0S1000 kit:
(center distance 235mm(9.3in))
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=160mm (6.3in)
L
Minimum AHU height: 535mm (21.1in)
L
Effective single upright flow-rate > 50kg/h (110lb/h)
H
H=200mm (7.9in) L=200mm (7.9in)
Minimum AHU height: 635mm (25.0in)
12
L
L
H
250 mm