Humidity

Operating altitude

Climate class

Degree of protection

Vibration resistance

Shock resistance

Mechanical load

Electromagnetic
compatibility

Process temperature range

Thermal shock

Process pressure range

26
Operation up to 100 %. Do not open in a condensing atmosphere.
As per IEC 61010-1 Ed.3:
• Up to 2 000 m (6 600 ft) above sea level
• Can be extended to 3 000 m (9 800 ft) above sea level if overvoltage protection is used
As per IEC 60068-2-38 test Z/AD
In accordance with DIN EN 60529, NEMA 250
IP66/IP68 NEMA 4x/6P
Types of housing:
• Single compartment; plastic
• Single compartment; aluminum, coated; Ex d/XP
• Single compartment; 316L, cast; Ex d/XP
• Dual compartment L-shaped, aluminum, coated; Ex d/XP
Ordering information: Select the required option in the "Electrical connection" order code.
Exclusion criteria are taken into account automatically.
If the "M12 plug" option is selected as electrical connection, then IP66/67 NEMA TYPE 4x is
valid for all housing types.
As per IEC60068-2-64-2009
a(RMS) = 50 m/s
2
, f = 5 to 2 000 Hz, t = 3 planes x 2 h
In accordance with IEC60068-2-27-2008: 300 m/s² [= 30 g
g
: standard acceleration of gravity
n
Support the device in the event of severe dynamic load. Maximum lateral loading capacity of the pipe
extensions and sensors: 75 Nm (55 lbf ft).
 Additional details in the "Support the device" section.
• Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation EMC (NE21)
• The requirements of EN 61326-3-1 for the safety function (SIL) are fulfilled
 Details are available in the supplementary Functional Safety Manual.

Process

• –60 to +230 °C (–76 to +446 °F)
• –60 to +280 °C (–76 to +536 °F)
• –50 to +230 °C (–58 to +446 °F) with PFA coating (conductive)
• 300 °C (572 °F) for a maximum of 50 h (cumulative)
Pay attention to the pressure and temperature dependence, see the "Sensor process pressure range"
section.
Without restrictions within the process temperature range.
With PFA coating (conductive): ≤ 120 K/s
WARNING
L
The maximum pressure for the measuring device is dependent on the lowest-rated element,
with regard to pressure, of the selected components. This means that it is necessary to pay
attention to the process connection as well as the sensor.
For pressure specifications, see the "Mechanical construction" section.
The measuring device must be operated only within the specified limits!
The Pressure Equipment Directive (2014/68/EU) uses the abbreviation "PS". The abbreviation "PS"
corresponds to the MWP (maximum working pressure) of the measuring device.
Liquiphant FTL64