Humidity
Operating altitude
Climate class
Degree of protection
Vibration resistance
Shock resistance
Mechanical load
Electromagnetic
compatibility
Process temperature range
Thermal shock
Process pressure range
26
Operation up to 100 %. Do not open in a condensing atmosphere.
As per IEC 61010-1 Ed.3:
• Up to 2 000 m (6 600 ft) above sea level
• Can be extended to 3 000 m (9 800 ft) above sea level if overvoltage protection is used
As per IEC 60068-2-38 test Z/AD
In accordance with DIN EN 60529, NEMA 250
IP66/IP68 NEMA 4x/6P
Types of housing:
• Single compartment; plastic
• Single compartment; aluminum, coated; Ex d/XP
• Single compartment; 316L, cast; Ex d/XP
• Dual compartment L-shaped, aluminum, coated; Ex d/XP
Ordering information: Select the required option in the "Electrical connection" order code.
Exclusion criteria are taken into account automatically.
If the "M12 plug" option is selected as electrical connection, then IP66/67 NEMA TYPE 4x is
valid for all housing types.
As per IEC60068-2-64-2009
a(RMS) = 50 m/s
2
, f = 5 to 2 000 Hz, t = 3 planes x 2 h
In accordance with IEC60068-2-27-2008: 300 m/s² [= 30 g
g
: standard acceleration of gravity
n
Support the device in the event of severe dynamic load. Maximum lateral loading capacity of the pipe
extensions and sensors: 75 Nm (55 lbf ft).
Additional details in the "Support the device" section.
• Electromagnetic compatibility as per EN 61326 series and NAMUR recommendation EMC (NE21)
• The requirements of EN 61326-3-1 for the safety function (SIL) are fulfilled
Details are available in the supplementary Functional Safety Manual.
Process
• –60 to +230 °C (–76 to +446 °F)
• –60 to +280 °C (–76 to +536 °F)
• –50 to +230 °C (–58 to +446 °F) with PFA coating (conductive)
• 300 °C (572 °F) for a maximum of 50 h (cumulative)
Pay attention to the pressure and temperature dependence, see the "Sensor process pressure range"
section.
Without restrictions within the process temperature range.
With PFA coating (conductive): ≤ 120 K/s
WARNING
L
The maximum pressure for the measuring device is dependent on the lowest-rated element,
with regard to pressure, of the selected components. This means that it is necessary to pay
attention to the process connection as well as the sensor.
‣
For pressure specifications, see the "Mechanical construction" section.
‣
The measuring device must be operated only within the specified limits!
‣
The Pressure Equipment Directive (2014/68/EU) uses the abbreviation "PS". The abbreviation "PS"
corresponds to the MWP (maximum working pressure) of the measuring device.
Liquiphant FTL64
] + 18 ms