Liquiphant FTL64

Terminal assignment

Connection cable

Endress+Hauser
 11
PFM output, electronic insert FEL67
7/
8: Nivotester FTL325P 1 CH, FTL325P 3 CH input 1
33/ 34: Nivotester FTL325P 3 CH input 2
37/ 38: Nivotester FTL325P 3 CH input 3
d4/ d2: Nivotester FTL375P input 1
z4/ z2: Nivotester FTL375P input 2
z6/ d6: Nivotester FTL375P input 3
• Maximum cable resistance: 25 Ω per core
• Maximum cable capacitance: < 100 nF
• Maximum cable length: 1 000 m (3 281 ft)
+
MAX
>0,7
COM
>0,5
MIN
1
2
1
2
7
8
33
34
37
38
d4
d2
z4
z2
z6
d6
L-
L+
-
.
A0036065
15