Clearances - Regency Fireplace Products Horizon HZ33CE-NG10 Owners & Installation Manual

Table of Contents

Advertisement

installation
|
10

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT
be recessed into combustible construction.
C
F
Clearance:
A: *Front Floor Clearance (min.)
B: *Sidewall (on one side)
C: *Ceiling
(room and/or alcove)
D: Alcove Width
E: Alcove Depth
F: Mantel
G: Mantel Clearances
10 |
®
Horizon
HZ33CE-10 Gas Fireplace
Dimension
Measured From:
0"
Underside of Unit
9" (229mm)
Side Opening of Unit
30" (762mm)
Top Opening of Unit
84" (1219mm)
Sidewall to Sidewall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
12" (305mm)
From Top Opening of Unit
15-3/4" (400mm)
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
C
Horizontal - Top
Horiztonal - Side
Horiztonal - Bottom
Vertical (Flex Vent)
Vertical (Rigid)
Close to Ceiling
Flue Clearances
2-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/4"