Solitrend MMP60
4
Assignment of the 10-pin plug
A
12 to 24 V
stabilized power supply
DC
Wire color: red (RD)
B
0 V
power supply
DC
Wire color: blue (BU)
D
1st analog positive (+), material moisture
Wire color: green (GN)
E
1st analog return line (-), material moisture
Wire color: yellow (YE)
F
RS485 A (must be enabled)
Wire color: white (WH)
G
RS485 B (must be enabled)
Wire color: brown (BN)
C
IMP-Bus RT
Wire color: gray (GY) / pink (PK), see figure below
J
IMP-Bus COM
Wire color: blue (BU) / red (RD), see figure below
K
2nd analog positive (+)
Wire color: pink (PK)
E
2nd analog return line (-)
Wire color: gray (GY)
H
Shield (is grounded at the device. The installation must be grounded correctly!)
Wire color: transparent
6.3
Post-connection check
Is the device or cable undamaged (visual inspection)?
Does the supply voltage match the specifications on the nameplate?
Are the connections established correctly and protected against mechanical influences?
Endress+Hauser
A
H
B
J
G
K
C
E
F
D
Electrical connection
A0037415