Modbus TCP Module
Installation Guide
Register
Description
30600
Product information
30601
Model number
30602
Reserved
30603
Reserved
30604
Starter state
30605
Current
30606
Current
30607
Motor temperature
30608
Power
Danfoss A/S © 2022.11
Bits
Details
0–5
Binary protocol version
6–8
Parameter list major version
9–15
Product type code:
4 = MCD 200
7 = MCD 500
0–7
Reserved
8–15
Soft starter model ID
0–4
0 = Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay, restart temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Uninitialized
1 = Initialized
7
0 = Hand on
1 = Auto on
8
Reserved
9
0 = Negative phase sequence
1 = Positive phase sequence
10–15
See the chapter Trip Codes
0–13
Average rms current across all 3 phases
14–15
Reserved
0–9
Current (% motor FLC)
10–15
Reserved
0–7
Motor thermal model (%)
8–15
Reserved
0–11
Power
12–13
Power scale
0 = Multiply power by 10 to get W
Modbus Registers
AN428736661763en-000101 / 175R1189 | 23