PDF format at sandc.com/en/support/ product-literature/ . Retain this This instruction sheet is a permanent part of your TripSaver II Cutout-Mounted Recloser. Designate a location where you can easily retrieve and refer to this publication. Instruction Sheet...
Understanding Several types of safety-alert messages may appear throughout this instruction sheet and on labels and tags attached to your TripSaver II Cutout-Mounted Recloser. Familiarize Safety-Alert yourself with these types of messages and the importance of these various signal words:...
Safety Information Location of Safety Labels DANGER TripSaver II may be energized from ® either side and in any position. Always consider all parts live until de-energized, tested, and grounded. G-9473-E Reorder Information for Safety Labels Safety Alert Message Description Part Number TripSaver®...
Safety Precautions DANGER The TripSaver II Cutout-Mounted Recloser operates at high voltage . Failure to observe these precautions will result in serious personal injury or death . Some of these precautions may differ from your company’s operating procedures and rules . Where a discrepancy exists, follow your company’s operating procedures and rules .
TripSaver II recloser magnet tool from its protective pouch when it is ready for use . Returning If for any reason a TripSaver II recloser magnet tool is to be returned, place the magnet tool in its carrying pouch to prevent damage during shipping. S&C Instruction Sheet 461-507...
TripSaver® II Service Center Configuration Software to view recloser status and event logs and to download snapshot files without taking their TripSaver II reclosers down. This tool also makes removal of the magnet easy. Follow these steps to attach a magnet to a TripSaver II Cutout-Mounted Recloser Applying the Magnet using the magnet tool.
Page 8
Figure 3. Raising the magnet tool up to the recloser. STEP 4. Move the magnet tool closer to TripSaver II recloser, aiming at the green S&C logo. See Figure 4. Figure 4. Moving the magnet tool closer to the recloser.
Page 9
II Service Center Configuration Software. NOTICE To power a TripSaver II recloser from its Sleep state, there must be enough load current available (1 A for 40-A continuous reclosers, 4 A for 100-A continuous reclosers, and 8 A for 200-A continuous reclosers) . When powered, the control can stay on as long as the power does not fall below the Stay On threshold (0 .5 A for 40-A continuous reclosers, 1 .5 A for 100-A continuous reclosers, and 3...
STEP 6. Flip the tool so the engraved S&C logo on the tool is facing away from you. Raise the magnet tool up to the left side of the TripSaver II recloser’s lower body. See Figure 6. Figure 6. Flipping the magnet tool and raising it up.
DO NOT perform a firmware or settings update in the field . Loss of line power or loss of packets caused by weak signal strength or interference may render the TripSaver II recloser nonfunctional . Reclosers must be taken down from the pole to perform firmware or settings updates using the Service Center Configuration Kit .