Installation Site Requirements Of The Outdoor Unit - Daikin RXP50N5V1B Installer's Reference Manual

Table of Contents

Advertisement

6
|
Unit installation

6.1.1 Installation site requirements of the outdoor unit

Installer reference guide
26
INFORMATION
Also read the following requirements:
"2 General safety
"7.1.3 Refrigerant piping length and height
Mind the following spacing guidelines:
>100
>350
b
a
b
a
>50
b
a
>50
a Air outlet
b Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit MUST be ≤1200 mm.
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and
NOT directly exposed to the wind.
4
precautions" [
 7].
>350
b
>100
a
>100
4
difference" [
 34].
a
>50
b
>100
a
>350
b
(mm)
4P519439-18T – 2022.06
RXF50~71D5V1B
R32 split series