9 Electrical installation
In this chapter
9.1 About connecting the electrical wiring
9.1.1 Precautions when connecting the electrical wiring
RXF50~71D5V1B
R32 split series
4P519439-18T – 2022.06
9.1
About connecting the electrical wiring ..................................................................................................................................
9.1.1
Precautions when connecting the electrical wiring ..............................................................................................
9.1.2
Guidelines when connecting the electrical wiring ................................................................................................
9.1.3
Specifications of standard wiring components .....................................................................................................
9.2
To connect the electrical wiring to the outdoor unit ............................................................................................................
Before connecting the electrical wiring
Make sure:
▪
The refrigerant piping is connected and checked
▪
The water piping is connected
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1
Making sure the power supply system complies with the electrical
specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor unit.
4
Connecting the main power supply.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by the power supply. Do NOT
touch them with bare hands.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you can touch electrical components.
For the location of the terminals, see the wiring diagram.
9
Electrical installation
|
Installer reference guide