13 Controller for heating circuits and DHW
53
Setting the time programm of the DHW.
By pressing
the start and stoptime appear.
Activate the times with
During the activated time, the boiler regulates to
the values indicated by the hot water sensor.
The hot water control is not activated outside the
set times!
Setting Outertemperature control.
Here you can set the temperature values for the
maximum and minimum boiler rating.
Adjustment range max. rated power -10° C bis +6°
C
Adjustment range min. power +7° C bis +25° C
Setting boiler rated power.
Enter the desired rated output of the boiler to
make a more accurate setting. This will improve
boiler runtime and modulation.
Installation Manual