Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. The standard pipe length is 5m (16'). The refrigerant should be charged
from the service port on the outdoor unit's low pressure valve. The additional refrigerant to be
charged can be calculated using the following formula:
Connective Pipe
Air Purging
Length (m)
< Standard pipe length Vacuum Pump
> Standard pipe
Vacuum Pump
length
CAUTION
DO NOT
DISPOSAL: Do not
dispose this product
as unsorted municipal
waste. Collection of
such waste separately
for special treatment
is necessary.
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Method
Liquid Side: Ø 6.35 (ø 0.25")
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 0.13oZ/ft
mix refrigerant types.
The european directive 2012/19 /UE on wasted
electrical and electronic equipments (WEEE), requires
that household electrical appliances must not be
disposed of in the normal unsorted municipal waste
stream. appliances must be collected separately in
order to optimize the recovery and recycling of the
materials they contain, and reduce the impact on
human health and the environment.
The crossed out "wheeled bin" symbol on the product
reminds you of your obligation, that when you disposed
of the appliances, it must be separately collected.
Consumers should contact their local authority or
retailer for information concerning the correct disposal
of their old appliance.
Additional Refrigerant
N/A
R32:
(Pipe length – standard length) x 0.26oZ/ft
34
Liquid Side: Ø 9.52 (ø 0.375")
R32:
(Pipe length – standard length) x 24g/m
V.2