Remark:The unit code is 75:kg/hour, 19:m3/hour.
Set primary command to flow rate.
Test of command:
Send command 1: FF FF FF FF FF 82 9A 1A AD 18 8C 01 00 3A ;to read the IEEE754 float
value of primary variable.
Receive command 1:FF FF FF FF FF 86 9A 1A AD 18 8C 01 07 00 00 13 00 00 00 00 2A

7.1.3 Command 2:Read primary variable's current and percentage value

Command formate:
Read the current and percent of the primary variable, the current of primary variable always match
the AO current output of the instrument. Percent is not restricted within 0~100%, if it is beyond the
limit of primary variable, it will find the limit fo the transmitter.
Request: None
Reponse:
Byte 0-3:
Byte 4-7:
Test of command:
Send command 2:FF FF FF FF FF 82 9A 1A AD 18 8C 02 00 39 ; to read the current and
primary variable percent of range.
Receive command 2:FF FF FF FF FF 86 9A 1A AD 18 8C 02 0A 00 00 40 80 00 00 00 00 00 00
F7

7.1.4 Command 3:Read primary variable current and dynamic variables

Command formate:
Read the current of primary variable and 4 preset dynamic variables at maximum. The current of
primary variable always match the AO output current of the instrument. Every type of device has a
definition on a relative dynamic variable, for example the secondary variable is temperature sensor.
Request: None
Response:
Byte 0-3:
Byte 4:
Byte 5-8:
Byte 9:
Byte 10-13: Secondary variable, IEEE 754
Byte 14:
Byte 15-18: Tertiary variable, IEEE 754
Byte 19:
Byte 20-23:
Remark:Primary variable is flow rate. The unit code is 75:kg/hour, 19:m3/hour;
Secondary variable is total flow. The unit code is 61:kg, 43:m3;
Date:24/04/2020
Analog output current mA, IEEE754
Percent of range , IEEE 754.
Analog output current mA, IEEE 754
Primary variable unit code
Primary variable, IEEE 754
Secondary variable unit code
Tertiary variable unit code
Quaternary variable unit code
Quaternary variable, IEEE 754
35 / 59
VFM-60
Vortex Flowmeter
Rev1.3
User's Manual