6.7 Examples of communication

The flowmeter's instrument Modbus address is 01, baud rate=4800 (C08=01, C09=05, C38=02).
Example 1: Read flow rate F,F=916.49 (4 bytes float)
Host command:
Flowmeter reponse: 01 03 04 44 65 1F CE 77 78
Example 2: Read total flow
Host command:
01 03 00 24 00 02 84 00
Flowmeter reponse:01 03 04 44 9D 1E 3F 36 9D
Example 3: Read all the value displayed on the flowmeter, including flow rate, frequency, pressure,
temperature, density, total flow ..... all together 13 value (52 bytes)
Host command:
01 03 00 00 00 1A c4 01
Flowmeter reponse:01 03 34
44 65 1F CE(flow rate=916.49)
42 48 00 00(frequency=50)
00 00 00 00(reserved=0)
00 00 00 00(pressure=0)
00 00 00 00(temperature=0)
3F 80 00 00(density=1.00)
00 00 00 00(reserved=0)
00 00 00 00(reserved)
00 00 00 00(reserved)
00 00 00 00(reserved)
00 00 04 E8(reserved=1256)
00 00 00 00(reserved=0)
Date:24/04/2020
The flow meter will take a long while to process the command. So
reponse this error code to prevent the host from processing a overtime
command.
is
To advise the host that the flowmeter is processing a command which
will takes a long time. So the host should resend the command when the
flowmeter is free.
01 03 00 00 00 02 C4 0B