User Guide
User Guide
SonoMeter 40
Ultrasonic energy meter SonoMeter 40
Ultrasonic energy meter
Test and calibration instruction
for heating and cooling applications
© Danfoss | Energy Meters | 2021.09
BC389148615526en-010101 | 1

Advertisement

loading

Summary of Contents for Danfoss SonoMeter 40

  • Page 1 User Guide User Guide SonoMeter 40 Ultrasonic energy meter SonoMeter 40 Ultrasonic energy meter Test and calibration instruction for heating and cooling applications © Danfoss | Energy Meters | 2021.09 BC389148615526en-010101 | 1...
  • Page 2 1.1 Activation of the test mode with the button .......................3 1.2 Activation of the test mode by short-circuiting the contacts ................. 4 1.3 Activation of test mode with software “SonoMeter 40 Configurator”..............5 2. Determination of measurement errors of the meter ..............6 2.1 Volume measuring errors determination test ......................6...
  • Page 3: General Information

    User Guide SonoMeter 40 General information This instruction is designed for the ultrasonic energy meter SonoMeter 40 for flow and energy verification and calibration. 1. Activation of the test The test mode can be activated in one of the following ways: mode 1.1.
  • Page 4 NOTE: when the test mode is activated by short-circuiting the contacts “SERVICE”, the volume and energy accumulated in the test mode are not added to the meter’s operating mode volume and energy readings. 4 | BC389148615526en-010101 © Danfoss | Energy Meters | 2021.09...
  • Page 5 User Guide SonoMeter 40 1.3. Activation of test The test mode can be activated via the optical interface using the software “SonoMeter 40 mode with software Configurator” and optical scan head in accordance with EN 62056-21 standard. In this case, optionally “SonoMeter 40...
  • Page 6 10 kJ/ pulse 2 kcal/ pulse 40 and 60 5 Wh/ pulse 20 kJ/ pulse 5 kcal/ pulse 0,6 and 1,0 10 Wh/ pulse 50 kJ/ pulse 10 kcal/ pulse 6 | BC389148615526en-010101 © Danfoss | Energy Meters | 2021.09...
  • Page 7 Meter calibration/adjustment allows to adjust the meter measurement of volume single point adjustment mode characteristics. It can be done by using the software “SonoMeter 40 Configurator” and optical scan head in accordance with EN 62056-21 standard. 1) The calibration/adjustment mode can be activated by removing protecting lid (2) of ADJ and shortcutting the pins.
  • Page 8 RESET Battery time – intended to reset the battery lifetime after replacement (the new battery replacement date will be calculated according to the set Battery lifetime value). OFF ADJ mode – intended for deactivation of the Adjustment mode. 8 | BC389148615526en-010101 © Danfoss | Energy Meters | 2021.09...