Maintenance; Remote Manual Pull Station - GILES Chester Fried CF 400 Operation And Service Manual

Table of Contents

Advertisement

Fire Suppression System
Install the fusible links listed below.
1. Fusible Link Installation, Cooking Surface
Model
Supplier
CF-400 VH
Globe
CF-500 VH
Globe
1.a. The fusible link in the plenum area of the hood (in front of exhaust fan) should be Ansul part # 56811
(165°F/74°C).
Tank
A 1.5 gallon tank, Ansul part #415900 is to be used with the system.
Charging Cylinder
101 Model 20 CO2 Cartridge, Ansul part #17492
Fire Damper
The fire damper has a 285°F (141°C) fusible link.
See the illustrations to help ensure safe and proper installation of your hood. If you have any ques-
tions concerning these procedures, contact your local representative or other qualified service per-
sons.

6 - 3 Remote Manual Pull Station

A remote manual pull station for the fire system may be required by local regulations in a path of exit or
egress. Ensure the pull station is clearly marked and easily accessible. Check with the authority having
jurisdiction for the requirements in your area.
See Giles Design Installation Recharge and Maintenance Manual for R-102 Restaurant Fire Suppression
System for complete installation instructions.

6 - 4 Maintenance

The fire extinguishing system should ne maintained as outlined in the Standard for Wet Chemical
Extinguishing Systems , NFPA 17A and the instructions of the installer's systems.
38
Part No.
Fusible Link Rating
317135
135°F (57°C)
317135
135°F (57°C)

Hide quick links: