5 Electrical installation
N
L
X2
X1
X2X1
a
a
Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.11
To connect the power
consumption digital inputs
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection
(voltage supplied by PCB)
[9.9] Power consumption control.
1 Open the following (see
"3.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Front panel
4 Main switch box cover
2 Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
Installation manual
20
unit" [ 4  6]):
1
2
4
3
5
4
3
2
a
Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
5.12
To connect the safety thermostat
(normally closed contact)
Wires: 2×0.75 mm²
Safety thermostat contact: 16 V DC detection (voltage
supplied by PCB)
[9.8.1]=3 (Benefit kWh power supply = Safety
thermostat)
1 Open the following (see
"3.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Installer switch box cover
2 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below.
1
a
unit" [ 4  6]):
1
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1C – 2020.07
3
2