5 Electrical installation

4.3.2

To connect the recirculation piping

Prerequisite: Only required if you need recirculation in your system.
1 Remove the top panel from the unit, see
unit" [ 4  6].
indoor
2 Cut out the rubber grommet on top of the unit, and remove the
stop. The recirculation connector is located below the space
heating/cooling water outlet pipe.
3 Route the recirculation piping through the grommet and connect
it to the recirculation connector.
4 Reattach the top panel.
4.3.3

To fill the space heating circuit

To fill the space heating circuit, use a field supply filling kit. Make
sure you comply with the applicable legislation.
NOTICE
▪ Air in the water circuit can cause malfunctioning of the
backup heater. During filling, it may not be possible to
remove all the air from the circuit. Remaining air will be
removed through the automatic air purge valves during
the initial operating hours of the system. Additional
filling with water afterwards may be required.
▪ To purge the system, use the special function as
described in the chapter
This function should be used to purge the heat
exchanger coil of the domestic hot water tank.
4.3.4

To fill the domestic hot water tank

1 Open every hot water tap in turn to purge air from the system
pipe work.
2 Open the cold water supply valve.
3 Close all water taps after all air is purged.
4 Check for water leaks.
5 Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.
4.3.5

To check for water leaks

Before insulating the water piping, it is important to detect water
leaks, in particular small leaks. Small leaks can easily be overseen,
but can cause damage to the unit and surroundings over a longer
period of time.
NOTICE
After water piping installation, check all connections for
leaks.
Installation manual
12
"3.2.1  To open the
[ 4   34].
"7  Commissioning" 
4.3.6

To insulate the water piping

The piping in the complete water circuit MUST be insulated to
prevent reduction of the heating capacity.
Consider that the space heating piping can condensate during
cooling operation. Foresee adequate insulation for these pipes.
5
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
5.1

About electrical compliance

For the models EGSAH/X06+10DA9W(G), the following statement...
Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
...is valid in the following cases:
(a)
#
Power supply
1 Combined power supply
(1N~, 50 Hz, 230 V AC)
C1
1N~, 50 Hz,
230 V AC
2 Split power supply
(2×(1N~, 50 Hz, 230 V AC))
1N~, 50 Hz,
230 V AC
C5
C1
1N~, 50 Hz,
230 V AC
(a)
For details of C1 and C5, see
supply" [ 4  13].
power
(b)
Normal operation: backup heater = maximum 3 kW
Emergency operation: backup heater = maximum 6 kW
EN/IEC  61000‑3‑12
(European/
(b)
Operation
Normal or emergency
Emergency
"5.3 To connect the main
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1C – 2020.07