Page 1
O P E R A T I N G I N S T R U C T I O N S nanoScan3 I/O Safety laser scanners...
Page 2
Original document This document is an original document of SICK AG. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
4.4.7 Restart interlock..............4.4.8 External device monitoring (EDM).......... 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 4
Enable propose field..............7.11 Inputs and outputs, local................. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Page 5
10.5 Replacing the system plug............... 104 10.6 Regular thorough check................105 Troubleshooting................. 106 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 6
List of figures..................137 List of tables..................139 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
The following symbols and conventions are used in this document: 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 8
Ö The LED is flashing. O The LED is illuminated continuously. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Make sure that the dangerous state of the machine is and remains switched off. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
You need suitable expertise and experience. You must be able to assess if the machine is operating safely. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Page 11
For maintenance, you must be able to assess if the machine is operating safely. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
(for example using a safe control or safety relays) and stop the dangerous state. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Angular resolution: the angular distance (in degrees) between 2 distance measurements 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
System plug The safety laser scanner requires a system plug. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
In access protection, people are detected if their whole body passes through the protective field. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Figure 8: Mobile hazardous area protection: detection of a person when a vehicle approaches 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Ensure that there are no small objects (e.g. cables) in the protective field of the safety laser scanner, even if they do not trigger a field interruption. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Length of the undetected area Width of the undetected area O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
"Data sheet", page 115 • d = set resolution 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
The required overrun (o) is calculated using the same formula as for hazardous point protection. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
= input delay for the control inputs in milliseconds (ms) ° 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Switching time between monitoring cases • Parameters specified based on the application O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Figure 15: Protection against reaching over with low scan plane (dimensions in mm) O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
TZ = tolerance range of the safety laser scanner, see "Data sheet", page 115 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
You must monitor a reference contour to protect the safety laser scanner from acciden‐ tal misalignment or manipulation. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
You must monitor a reference contour to protect the safety laser scanner from acciden‐ tal misalignment or manipulation. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
The multiple sampling must be 2 or 3. Otherwise, a person could possibly walk unde‐ tected through the protective field. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
This is based on the assumption that the person recognizes the danger and stands still. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Figure 24: Stopping distance as a function of the vehicle’s speed Speed Stopping distance 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 36
The scan plane must be at a maximum height of 200 mm everywhere. Otherwise, persons lying horizontally may not be detected. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Power is supplied to all electrically connected devices in accordance with SELV/ PELV (IEC 60204-1). 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
The electrical power supply has an appropriate electrical fuse. Further topics • "Data sheet", page 115 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Figure 27: Dual-channel and isolated connection of an OSSD pair 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
• 1-out-of-n evaluation (only devices with several static control inputs) O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
"Settings for monitoring case tables", page 82 • "Configure switching sequence", page 82 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Possible signals are, for example: reset required, contamination warning. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
After the reset, the operator can restart the machine in a second step. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Figure 30: How the restart interlock works (2): person detected in protective field, safety output in OFF state O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
The external device monitoring (EDM) monitors the status of downstream contactors. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
• "Visual check of the machine and the protective device", page 49 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
If a number of protective fields are used (in different monitoring cases for exam‐ ple), check the edges of all protective fields. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Page 49
Are there any objects (e.g. cables, reflective surfaces) in the protective field? ° 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 50
O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Screw in the system plug using the captive screws. Tightening torque: 1.3 Nm. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
"Dimensional drawings", page 124 • "Accessories", page 127 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Figure 34: Connecting cable (male connector, M12, 8-pin, A-coded) 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Universal output: contamination, fault, reset required (OSSD pair 1), monitoring result O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Page 55
OSSD pair 2), sleep mode, restarting the device Not connected Thread Functional earth/shield 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
• Universal input: sleep mode, restarting the device O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Send data - RX– Receive data - Thread Shielding 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
You first need to assign the device a valid network address. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Figure 37: Software controls Menu bar Toolbar Main navigation 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Changing the password of the Maintenance personnel user group is allowed. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Device Catalog. The devices are displayed as Device tiles in the working range. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
To configure the device, perform diagnostics or create reports, open a device window. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Flying leads (2 m) NANSX-AACCAEZZ1 • M12 Ethernet con‐ nection 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Functional scope of the configuration in the device: • Serial number: • Hardware version: O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
The type of application depends on the application of the safety laser scanner: • Mobile O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Here you can configure the reference contour field required for your application. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
7.10 Fields Overview Figure 41: Field editor Toolbar O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Calculate field Zoom in Zoom out Zoom to area 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
If necessary, you can make changes to each individually at a later date. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Polygon: each point individually • Contour line: each point individually 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Based on the data obtained, the Safety Designer suggests the contour and size of the field. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Further topics • "Distance from walls", page 28 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
You can assign the desired signals to the individual pins or wires via drag-and-drop. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Signal from the auxiliary contacts of the positively guided contactors for external device monitoring (EDM). 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
For dynamic inputs, you must specify for each incremental encoder how many pulses it outputs per distance traveled. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Field set in the monitoring case and in the cut-off path 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Combinations which are invalid or already assigned are marked. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
If you have not assigned fields to certain cells in a monitoring case table, Safety Designer automatically assigns the Always OFFfunction to these cells. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
You can move fields to the foreground or to the background using the context menu (right mouse button). 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Stop the safety function Click on the button. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
The required data are included in the report. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
The password of the Administrator user group is reset to the factory settings. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
The calibration process starts. Typically, this process can take up to a minute. A 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 92
✓ The end of the calibration is shown. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
When the start procedure is complete, the status LEDs and the display show the safety laser scanner’s current operational status. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Carry out the checks specified in the test plan of the manufacturer of the machine and the operating entity. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Network LED 1 Network LED 2 Network LED 3 Button 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Press the button briefly to change between a number of pages with detailed information. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 98
All safety outputs in the OFF state. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Page 99
Press the button to obtain more informa‐ tion. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
• "Thorough check of the principal function of the protective device", page 48 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
USB connection is closed with the protective cover. Prerequisites Tool required: • TX10 key 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 102
O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Mount the system plug on the new safety laser scanner. Mount the new safety laser scanner. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Enclosure rating IP65 only applies if the optics cover and the system plug are mounted and the USB connection is closed with the protective cover. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Carry out the checks specified in the test plan of the manufacturer of the machine and the operating entity. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Check the working process of the control input. machine. b Check speed source. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 108
O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
The USB connection may only be used temporarily and only for configuration and diagnostics. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
• Check where a person can stay or when a person is detected O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
The internal memory of the safety laser scanner is cleared when it is restarted. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 112
For each duration, the diagram shows the corresponding number of object detections. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
Print message history Save message history as a PDF 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
SICK will be glad to help you dispose of these devices on request. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
"Sensing range", page 121 tour detection field Warning field range ≤ 10 m 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
≤ 12 Mbit/s (Full Speed) Length of cable ≤ 3 m O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Static control input, universal input, universal I/O (configured as input) 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
RAL 9005 (black) and RAL 1021 (rape yellow) Optics cover material Polycarbonate O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Wavelength 905 nm Detectable remission 1.8% to several 1,000% 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Make sure that the machine’s control does not react to these test pulses and the machine does not switch off. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
50 mm 2.15 m 40 mm 1.60 m 30 mm 1.25 m 20 mm 1.25 m 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 122
Required minimum size of the object in mm Scanning range in m O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Page 123
Gray cardboard Writing paper White plaster Reflectors > 2,000%, reflective tapes > 300% 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
If the viewing slit is longer (a > 200 mm), a case-by-case consideration is required. Contact the responsible SICK subsidiary. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
A system plug is required to operate the safety laser scanner, see "System plug", page 127. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Part number Optics cover (with seal and screws) 2111696 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Bend radius (with fixed installation) ≥ 46 mm , bend radius (with flexible installation) ≥ 92 mm 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Test rod 70 mm 2095139 Test rod holder 4096204 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
OSSDs are switched off. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 130
O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Page 131
Safety integrity level SILCL SIL claim limit (IEC 62061) 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 132
The warning field must not be used for safety applications. O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
IEC 61496-3 GB 19436.3 IEC 61508 GB/T 20438 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 134
ISO 13849-1 GB/T 16855.1 ISO 13855 GB/T 19876 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK Subject to change without notice...
Printed copies of the license texts are also available on request. 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
45. Monitoring cases......................81 46. Simulation........................85 47. Data output......................... 86 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 138
57. Range and required remission for measured data output........123 58. Dimensional drawing....................124 O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O 8024596/1H31/2022-08-29 | SICK...
42. Ordering information, test rods................128 43. Note on standards....................133 8024596/1H31/2022-08-29 | SICK O P E R A T I N G I N S T R U C T I O N S | nanoScan3 I/O Subject to change without notice...
Page 140
E-Mail office@sick.com.gr E-Mail info@sick.ru Vietnam Hong Kong Singapore Phone +65 6744 3732 Phone +852 2153 6300 Phone +65 6744 3732 E-Mail sales.gsg@sick.com E-Mail ghk@sick.com.hk E-Mail sales.gsg@sick.com Detailed addresses and further locations at www.sick.com SICK AG | Waldkirch | Germany | www.sick.com...