Mitsubishi MELSEC QS Series Programming Manual page 181

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

Error
Code
Error Contents and Cause
(SD0)
• The same network number is used for
Ethernet, CC-Link IE controller
network, and MELSECNET/H.
• The network number, station number,
and/or group number set in Network
3104
parameter are out of the setting
range.
• The specified I/O number is outside
the range of the used CPU module.
• The Ethernet inherent parameter
setting is incorrect.
• Though the number of CC-Link
modules set in the network
parameters is one or more, the
number of actually mounted modules
is zero.
• The start I/O number in the common
3105
parameters is different from that of
the actually mounted module.
• The station type of the CC-Link
module count setting parameters is
different from that of the actually
mounted station.
• The network refresh parameter for
CC-Link is out of range.
• Although the safety remote station set
in the network parameter does not
3106
support the safety data monitoring
time, it is set for the station.
The safety data monitoring time has
been set.
The CC-Link parameter setting is
3107
incorrect.
The start I/O number of the target
3400
module in Remote password is set to
other than 0
to 3E0
H
Ethernet module of function version B
or later is not mounted on the slot
3401
specified for the start I/O number of
Remote password.
*1 :For the module whose first five digits of serial number are "10031" or earlier.
• Correct the parameter setting and
write Network parameter to the CPU
module.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
• Check the parameter setting.
• Check the [Model name] and [Module
technical version] of the safety
remote station settings, or delete the
setting of the safety data monitoring
time.
Delete the setting of the safety data
monitoring time.
Check the parameter setting.
Change the start I/O number of the
target module to the number within 0
.
3E0
H
H
Mount the Ethernet module of function
version B or later on the slot specified
for the start I/O number of Remote
password.
Corrective Action
.
9.1 Error Code List
9.1.5 Error code list (3000 to 3999)
Corresponding
CPU
QS
QS
QS
*1
QS
QS
to
QS
H
QS
9-21
9